No comment |
H5AN-4D AC100-240 OMRON Time Relay NEWOMRON Time Relay H5AN-4D AC100-240
Product Description:
Wide time range from 1/100 seconds to 9999 hrs.
Built-in power supply incorporated in timer enables direct connection of sensors and other components.
Draw-out construction allows maintenance without disconnecting the wiring.
Power supply freely selectable within a range of 100 to 240 VAC; a DC-operated version is also available.
Control outputs of both contact type and solid-state type simultaneously available.
Seven operating modes (N, F, C, R, K, P, and Q) are available.
Specifications:
Ratings
Item
H5AN-4D/H5AN-4DM
Rated supply voltage
H5AN-4D: 100 to 240 VAC (50/60 Hz),
12 to 24, 48, or 100 VDC (permissible ripple: 20% max.)
H5AN-4DM: 100 to 240 VAC (50/60 Hz)
12 to 24 VDC (permissible ripple: 20% max.)
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
Approx. 10 VA (at 240 VAC, 50 Hz), approx. 5 W (at 24 VDC)
Resetting system and gate input
Reset by power-OFF: min. power OFF time: 0.5 s
External reset or gate (common to contact and solid-state inputs): min. reset input signal width: 0.02 s
One-shot output time
0.1 to 1 s (adjustable)
Control outputs
Contact output: SPDT, 3 A at 250 VAC, resistive load (cosΦ = 1)
Solid-state output: Open collector, 100 mA max. at 30 VDC max.
Power supply for externally connected components
12 VDC±10%, 80 mA (permissible ripple: 5% max.)
Note: Inrush current was measured within the range shown below.
Characteristics
Accuracy of operating time
±0.01% ±0.05 s max. (power OFF start), ±0.005% ±0.03 s max. (reset start) (see note)
Setting error
Influence of voltage
Influence of temperature
Insulation resistance
100 MΩ min. (at 500 VDC) (between current-carrying terminal and exposed non-current carrying metal
parts, between non-continuous contacts)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying metal parts)
750 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction: 300 m/s2 (approx. 30G)
Malfunction: 100 m/s2 (approx. 10G)
Ambient temperature
Operating: -10°C to 55°C
Storage: -25°C to 65°C
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)
Approved standards
UL (File No. E41515), CSA (File No. LR22310)
Weight
Approx. 360 g
Note: This value denotes the average of the repeat accuracy, setting error, and variations due to voltage and temperature changes. It includes the rise time of the power supply, and the operating time of the internal and output circuits.
No comment |