No comment |
H3RN-2 24VDC OMRON RELAY NewProduct Description?
Ratings
Rated supply voltage
12 VDC
Operating voltage range
90% to 110% of rated supply voltage
Power consumption (Relay ON)
0.5 W (at 12 VDC)
Power consumption (Relay OFF)
0.2 W (at 12 VDC)
Reset voltage
10% max. of rated supply voltage
Number of time ranges
4
Time ranges
0.1 s to 1 s, 1 s to 10 s, 0.1 min to 1 min, 1 min to 10 min
Operating mode
ON delay, Flicker OFF start, Flicker ON start, Interval, Pulse Operation(use in interval mode, connect power supply terminals as pulse operation)
Control output Type
Relay output (DPDT)
Control output (Contact output)
Switching capacities (resistive load (cos(phi)=1)): 250 VAC 3 A
Minimum applicable load: 10 mA at 5 VDC (failure level: P)Ambient temperature
Operating: -10 to 55 CEL
Storage: -25 to 65 CEL
(with no icing)Ambient humidity
Operating: 35 to 85%
Characteristics
Accuracy of operating time
+/-1 % (FS) max. (+/-1% +/-10 ms max. in a ragen of 1 s)
Setting error
-15 to 15% (FS) -50 to 50 ms max.
Reset time
0.1 s max. (including halfway reset)
Influence of voltage
+/-2% FS max.
Influence of temperature
+/-2% FS max.
Insulation resistance
100 MOhm min. (at 500 VDC)
Dielectric strength
between contacts of different polarities: 2000 VAC, 50/60 Hz for 1 min
between operating power circuit and control output: 2000 VAC, 50/60 Hz for 1 min
between non-continuous contacts: 1000 VAC, 50/60 Hz for 1 minImpulse withstand voltage
between power terminals: 1 kV
Noise immunity
+/-1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 us, 1-ns rise)
Static immunity
Mulfunction: 4 kV Destruction: 8 kV
Vibration resistance (Destruction)
10 to 55 Hz, 0.75 mm single amplitude each in X, Y, and Z directions for 1 hours
Vibration resistance (Malfunction)
10 to 55 Hz, 0.5 mm single amplitude each in X, Y, and Z directions for 10min
Shock resistance (Destruction)
980 m/s2 3 times each 6 directions
Shock resistance (Malfunction)
100 m/s2 3 times each 6 directions
Mechanical Life expectancy (relay output)
10000000 operations min. (under no load at 1800 operations/h)
Electrical Life expectancy (relay output)
100000 operations min.(3 A at 250 VAC, resistive load at 1800 operations/h)
Degree of protection
IEC60529(JEM): IP40(excluding terminal section)
Applicable standard (UL)
Standard No.: UL508
File number: E41515Applicable standard (CSA)
Standard No.: CSA C22.2 No.14
File number: LR22310Applicable standard (EC Directive (Low Voltage Directive) )
EN61812-1
IEC60664-1 4 kV/2Applicable standard (EC Directive (EMC Directive) )
EMI: EN61812-1
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
EMS: EN61812-1
Immunity ESD: IEC61000-4-2(6 kV contact discharge, 8 kV air discharge)
cRF-interference: IEC61000-4-3(10 V/m, AM radio waves (80 MHz to 1 GHz))
Immunity Burst: IEC61000-4-4(2 kV power-line, 2 kV I/O signal-line)
Immunity Surge: IEC61000-4-5(1 kV line to line, 2 kV line to ground)External connection method
Plug-in terminal
Case color
Munsell 5Y7/1(Light gray)
Weight
Approx. 18 g
No comment |