We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

H3RN-2 24VDC RELAY New

H3RN-2 24VDC  RELAY  New
H3RN-2 24VDC  RELAY  New
H3RN-2 24VDC  RELAY  New
H3RN-2 24VDC  RELAY  New
H3RN-2 24VDC RELAY New
H3RN-2 24VDC OMRON RELAY NewProduct Description?RatingsRated supply voltage12 VDCOperating voltage r... Read More
$14.00
Ex Tax: $14.00
  • Stock: In Stock
  • Model: H3RN-2
  • Weight: 0.10kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: H3RN-2
H3RN-2 24VDC OMRON RELAY New

Product Description?

Ratings

Rated supply voltage

12 VDC

Operating voltage range

90% to 110% of rated supply voltage

Power consumption (Relay ON)

0.5 W (at 12 VDC)

Power consumption (Relay OFF)

0.2 W (at 12 VDC)

Reset voltage

10% max. of rated supply voltage

Number of time ranges

4

Time ranges

0.1 s to 1 s, 1 s to 10 s, 0.1 min to 1 min, 1 min to 10 min

Operating mode

ON delay, Flicker OFF start, Flicker ON start, Interval, Pulse Operation(use in interval mode, connect power supply terminals as pulse operation)

Control output Type

Relay output (DPDT)

Control output (Contact output)

Switching capacities (resistive load (cos(phi)=1)): 250 VAC 3 A
Minimum applicable load: 10 mA at 5 VDC (failure level: P)

Ambient temperature

Operating: -10 to 55 CEL
Storage: -25 to 65 CEL
(with no icing)

Ambient humidity

Operating: 35 to 85%

Characteristics

Accuracy of operating time

+/-1 % (FS) max. (+/-1% +/-10 ms max. in a ragen of 1 s)

Setting error

-15 to 15% (FS) -50 to 50 ms max.

Reset time

0.1 s max. (including halfway reset)

Influence of voltage

+/-2% FS max.

Influence of temperature

+/-2% FS max.

Insulation resistance

100 MOhm min. (at 500 VDC)

Dielectric strength

between contacts of different polarities: 2000 VAC, 50/60 Hz for 1 min
between operating power circuit and control output: 2000 VAC, 50/60 Hz for 1 min
between non-continuous contacts: 1000 VAC, 50/60 Hz for 1 min

Impulse withstand voltage

between power terminals: 1 kV

Noise immunity

+/-1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 us, 1-ns rise)

Static immunity

Mulfunction: 4 kV Destruction: 8 kV

Vibration resistance (Destruction)

10 to 55 Hz, 0.75 mm single amplitude each in X, Y, and Z directions for 1 hours

Vibration resistance (Malfunction)

10 to 55 Hz, 0.5 mm single amplitude each in X, Y, and Z directions for 10min

Shock resistance (Destruction)

980 m/s2 3 times each 6 directions

Shock resistance (Malfunction)

100 m/s2 3 times each 6 directions

Mechanical Life expectancy (relay output)

10000000 operations min. (under no load at 1800 operations/h)

Electrical Life expectancy (relay output)

100000 operations min.(3 A at 250 VAC, resistive load at 1800 operations/h)

Degree of protection

IEC60529(JEM): IP40(excluding terminal section)

Applicable standard (UL)

Standard No.: UL508
File number: E41515

Applicable standard (CSA)

Standard No.: CSA C22.2 No.14
File number: LR22310

Applicable standard (EC Directive (Low Voltage Directive) )

EN61812-1
IEC60664-1 4 kV/2

Applicable standard (EC Directive (EMC Directive) )

EMI: EN61812-1
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
EMS: EN61812-1
Immunity ESD: IEC61000-4-2(6 kV contact discharge, 8 kV air discharge)
cRF-interference: IEC61000-4-3(10 V/m, AM radio waves (80 MHz to 1 GHz))
Immunity Burst: IEC61000-4-4(2 kV power-line, 2 kV I/O signal-line)
Immunity Surge: IEC61000-4-5(1 kV line to line, 2 kV line to ground)

External connection method

Plug-in terminal

Case color

Munsell 5Y7/1(Light gray)

Weight

Approx. 18 g

 