No comment |
Product Description?
Lockable test button models now available.
Built-in mechanical operation indicator.
Provided with nameplate.
AC type is equipped with a coil-disconnection self-diagnostic function (LED type).
High switching power (1-pole: 10 A).
Environment-friendly (Cd, Pb free).
Wide range of Sockets also available.
Specifications:
Rated voltage | Rated current* | Coil | Coil inductance (H) | Must | Must | Max. | Power | ||||||
50 Hz | 60 Hz | Armature | Armature | % of rated voltage | |||||||||
AC | 24 V | 43.5 mA | 37.4 mA | 253 Ω | 0.81 | 1.55 | 80% max. | 30% max. | 110% | 0.9 VA at 60 Hz | |||
110 V | 9.5 mA | 8.2 mA | 5,566 Ω | 13.33 | 26.83 | ||||||||
120 V | 8.6 mA | 7.5 mA | 7,286 Ω | 16.13 | 32.46 | ||||||||
230 V | 4.4 mA | 3.8 mA | 27,172 Ω | 72.68 | 143.9 | ||||||||
240 V | 3.7 mA | 3.2 mA | 30,360 Ω | 90.58 | 182.34 | ||||||||
Rated voltage | Rated current* | Coil | Coil inductance (H) | Must | Must | Max. | Power | ||||||
Armature | Armature | % of rated voltage | |||||||||||
DC | 6 V | 87.0 mA | 69 Ω | 0.25 | 0.48 | 70% max. | 15% min. | 110% | 0.53 W | ||||
12 V | 43.2 mA | 278 Ω | 0.98 | 2.35 | |||||||||
24 V | 21.6 mA | 1,113 Ω | 3.6 | 8.25 | |||||||||
48 V | 11.4 mA | 4,220 Ω | 15.2 | 29.82 | |||||||||
*The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±10%.
Contact Ratings
Number of poles | 1 pole | 2 poles | ||
Load | Resistive load | Inductive load | Resistive load | Inductive load |
Rated load | 10 A at 250 VAC; | 7.5 A at 250 VAC; | 5 A at 250 VAC; | 2 A at 250 VAC; |
Rated carry current | 10 A | 5 A | ||
Max. switching voltage | 440 VAC, 125 VDC | 380 VAC, 125 VDC | ||
Max. switching current | 10 A | 5 A | ||
Max. switching power | 2,500 VA, 300 W | 1,875 VA, 150 W | 1,250 VA, 150 W | 500 VA, 90 W |
Failure rate (reference value) | 100 mA at 5 VDC | 10 mA at 5 VDC |
Note:P level: λ60 = 0.1 x 10-6/operation
G2R-1-DC12V OMRON RELAY New
Product Description?
Lockable test button models now available.
Built-in mechanical operation indicator.
Provided with nameplate.
AC type is equipped with a coil-disconnection self-diagnostic function (LED type).
High switching power (1-pole: 10 A).
Environment-friendly (Cd, Pb free).
Wide range of Sockets also available.
Specifications:
Rated voltage
Rated current*
Coil
resistance*Coil inductance (H)
(ref. value)Must
operate
voltageMust
release
voltageMax.
voltagePower
consumption
(approx.)50 Hz
60 Hz
Armature
OFFArmature
ON% of rated voltage
AC
24 V
43.5 mA
37.4 mA
253 Ω
0.81
1.55
80% max.
30% max.
110%
0.9 VA at 60 Hz
110 V
9.5 mA
8.2 mA
5,566 Ω
13.33
26.83
120 V
8.6 mA
7.5 mA
7,286 Ω
16.13
32.46
230 V
4.4 mA
3.8 mA
27,172 Ω
72.68
143.9
240 V
3.7 mA
3.2 mA
30,360 Ω
90.58
182.34
Rated voltage
Rated current*
Coil
resistance*Coil inductance (H)
(ref. value)Must
operate
voltageMust
release
voltageMax.
voltagePower
consumption
(approx.)Armature
OFFArmature
ON% of rated voltage
DC
6 V
87.0 mA
69 Ω
0.25
0.48
70% max.
15% min.
110%
0.53 W
12 V
43.2 mA
278 Ω
0.98
2.35
24 V
21.6 mA
1,113 Ω
3.6
8.25
48 V
11.4 mA
4,220 Ω
15.2
29.82
*The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±10%.
Contact Ratings
Number of poles
1 pole
2 poles
Load
Resistive load
(cosΦ = 1)Inductive load
(cosΦ = 0.4; L/R = 7 ms)Resistive load
(cosΦ = 1)Inductive load
(cosΦ = 0.4; L/R = 7 ms)Rated load
10 A at 250 VAC;
10 A at 30 VDC7.5 A at 250 VAC;
5 A at 30 VDC5 A at 250 VAC;
5 A at 30 VDC2 A at 250 VAC;
3 A at 30 VDCRated carry current
10 A
5 A
Max. switching voltage
440 VAC, 125 VDC
380 VAC, 125 VDC
Max. switching current
10 A
5 A
Max. switching power
2,500 VA, 300 W
1,875 VA, 150 W
1,250 VA, 150 W
500 VA, 90 W
Failure rate (reference value)
100 mA at 5 VDC
10 mA at 5 VDC
Note:P level: λ60 = 0.1 x 10-6/operation
No comment |