Your Position: Home > Low Voltage > Relay > G2R-1-E 120VAC RELAY New

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

G2R-1-E 120VAC RELAY New

prevnext

G2R-1-E 120VAC  RELAY  New
  • NO.:
  • Weight: 21gram
  • Market price: $ 6.6
  • Shop price: $ 2.0
  • Goods click count: 360
  • Total:
  • Quantity:
Add to cart collect
  

Description

G2R-1-E 120VAC OMRON RELAY New

 

Product Description?

Lockable test button models now available.

Built-in mechanical operation indicator.

Provided with nameplate.

AC type is equipped with a coil-disconnection self-diagnostic function (LED type).

High switching power (1-pole: 10 A).

Environment-friendly (Cd, Pb free).

Wide range of Sockets also available.

Specifications:

Rated voltage

Rated current*

Coil
resistance*

Coil inductance (H)
(ref. value)

Must
operate
voltage

Must
release
voltage

Max.
voltage

Power
consumption
(approx.)

50 Hz

60 Hz

Armature
OFF

Armature
ON

% of rated voltage

AC

24 V

43.5 mA

37.4 mA

253 Ω

0.81

1.55

80% max.

30% max.

110%

0.9 VA at 60 Hz

110 V

9.5 mA

8.2 mA

5,566 Ω

13.33

26.83

120 V

8.6 mA

7.5 mA

7,286 Ω

16.13

32.46

230 V

4.4 mA

3.8 mA

27,172 Ω

72.68

143.9

240 V

3.7 mA

3.2 mA

30,360 Ω

90.58

182.34

Rated voltage

Rated current*

Coil
resistance*

Coil inductance (H)
(ref. value)

Must
operate
voltage

Must
release
voltage

Max.
voltage

Power
consumption
(approx.)

Armature
OFF

Armature
ON

% of rated voltage

DC

6 V

87.0 mA

69 Ω

0.25

0.48

70% max.

15% min.

110%

0.53 W

12 V

43.2 mA

278 Ω

0.98

2.35

24 V

21.6 mA

1,113 Ω

3.6

8.25

48 V

11.4 mA

4,220 Ω

15.2

29.82

              

*The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±10%.

Contact Ratings

Number of poles

1 pole

2 poles

Load

Resistive load
(cosΦ = 1)

Inductive load
(cosΦ = 0.4; L/R = 7 ms)

Resistive load
(cosΦ = 1)

Inductive load
(cosΦ = 0.4; L/R = 7 ms)

Rated load

10 A at 250 VAC;
10 A at 30 VDC

7.5 A at 250 VAC;
5 A at 30 VDC

5 A at 250 VAC;
5 A at 30 VDC

2 A at 250 VAC;
3 A at 30 VDC

Rated carry current

10 A

5 A

Max. switching voltage

440 VAC, 125 VDC

380 VAC, 125 VDC

Max. switching current

10 A

5 A

Max. switching power

2,500 VA, 300 W

1,875 VA, 150 W

1,250 VA, 150 W

500 VA, 90 W

Failure rate (reference value)

100 mA at 5 VDC

10 mA at 5 VDC

Note:P level: λ60 = 0.1 x 10-6/operation




























  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: