Introduction
Thank you for choosing Delta DVP-Slim series programmable logic controller. DVP-Slim series pin-headed digital I/O extension unit offers 32 points. For DVP-SS/SA/SX/SC series MPU, the maximum digital I/O extension points (including the MPU) can reach 128 points. For SV series MPU, the maximum digial I/O extension points (including the MPU) can reach 256 points. In addition, maximum 8 additional special modules (AD/DA/PT/TC/XA/PU) can be extended to DVP-Slim series extension unit.
Electrical Specification
Model
Item
DVP32SM11N
DVP32SN11TN
Power supply voltage
24V DC (-15% ~ 20%) (with DC input polarity reverse protection)
Motion specification
Within 5ms of the momentary power loss, the device will keep on operating.
Power consumption
1W
1.5W
Insulation resistance
>5 Mohm (all I/O point-to-ground: 500V DC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Earth
The diameter of grounding wire shall not be less than that of L, N terminal of the power. (When many PLCs are in use at the same time, please make sure every PLC
Is properly grounded.)
Operation/storage
environment
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Shock/vibration
immunity
International standards: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
70g
70g
Model explanation