No comment |
>
Control System >
PLC >
Delta PLC >
DVP04TC-H2 Delta PLC 4 point 0.1 degree resolution Analog Module Original brand newDVP04TC-H2 Delta PLC 4 point 0.1 degree resolution Analog Module Original brand new
Features
DVP04TC-H2 is able to receive 4 points 0~150mV voltage input of thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type, E-type, N-type) and convert them into 24-bit digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04TC-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04TC-H2 displays temperatures in Celsius and Fahrenheit (resolution: 0.1°F).
Specification
Temperature
measurement module
Explanation
Power supply voltage
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog output channel
4 channels/module
Applicable sensor types
J-type, K-type, R-type, S-type, T-type, E-type, N-type Floating thermocouple sensor, 0~150mV voltage input.
Range of input temp.
See the table in section Temperature / Digital Curve
Range of digital conversion
See the table in section Temperature / Digital Curve
Resolution
24 bits (0.1°C/0.1°F)
Overall accuracy
+ - 0.6% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response time
200ms × the number of channels
Isolation
Isolation between digital circuits and analog circuits. Isolation between channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Digital data format
15 significant bits out of 16 bits are available; in 2’s complement
Average function
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K100
Self-diagnosis
Upper and lower bound detection/channel
Communication mode (RS-485)
ASCII/RTU mode. Communication speed: 4,800 / 9,600 / 19,200 /
38,400 / 57,600 / 115,200 bps. ASCII data format: 7-bit, even bit, 1
stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1).
RS-485 cannot be used when connected to PLC MPU.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Max. rated power consumption
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power.
Operation/storage
1. Operation: 0°C~ 55°C (Temperature), 50 ~ 95% (Humidity), pollution degree 2
2. Storage: -25°C~ 70°C (Temperature), 5 ~ 95%(Humidity)
Vibration/shock immunity
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Product Profile & Dimension
No comment |