No comment |
G7T-1122S OMRON RELAY NewProduct Description?
Product classification
Monostable relays
Standard typeCoil ratings
12 VDC 42 mA
Coil resistance
290 Ohm
Operate voltage (Set voltage)
80% Max.
Release voltage (Reset voltage)
10% Min.
Max. voltage
110% (of rated voltage)
Power consumption (Single stable)
0.5 W
Operating indicator
Mech indicator
Coil surge killer
Not equipped
Contact Type
SPST-NO
Contact method
Bifurcated crossbar
Contact material
Contact body material: Ag
Contact finish: AgAu-cladContact rated load
220 VAC 2 A (Resistive load)
220 VAC 1 A (Inductive load (cos phi = 0.4))
24 VDC 1 A (Resistive load)
24 VDC 0.5 A (Inductive load (L/R = 7 ms))Maximum switching voltage
250 VAC (Resistive load)
250 VAC (Inductive load (cos phi = 0.4))
125 VDC (Resistive load)
125 VDC (Inductive load (L/R = 7 ms))Maximum switching current
AC: 1 A (Resistive load)
AC: 1 A (Inductive load (cos phi = 0.4))
DC: 1 A (Resistive load)
DC: 1 A (Inductive load (L/R = 7 ms))Maximum switching power
AC: 110 VA (Resistive load)
DC: 24 W (Resistive load)
DC: 12 W (Inductive load (L/R = 7 ms))Failure rate
100 uA at 1 VDC (failure level: P Reference value)
Ambient temperature
Operating: -40 to 70 CEL
(with no icing or condensation)Ambient humidity
Operating: 5 to 85% RH
(with no icing or condensation)Characteristics
Contact resistance
Max. 50 mOhm, Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A
Operating time (set time)
15 ms Max.
Release time (Reset time)
15 ms Max.
Max.operating frequency (Mechanical)
18000 opn./h
Max.operating frequency (Erectrical)
1800 opn./h
Insulation resistance
Between coil and contacts: 100 MOhm Min. (at 500 VDC)
Between contacts of same polarity: 100 MOhm Min. (at 500 VDC)Dielectric strength
Between coil and contacts: 2000 VAC 50/60 Hz for 1 min (Leakage current 2 mA 50/60 Hz 1 min)
Between contacts of same polarity: 1000 VAC 50/60 Hz for 1 min (Leakage current 2 mA 50/60 Hz 1 min)Vibration resistance (Destruction)
10 to 55 to 10 Hz 0.5-mm single amplitude (1.0-mm double amplitude) for 2 hours each in X, Y, and Z directions (No defect in appearance and construction after applying variable vibration in each directions for 2 hours.)
Vibration resistance (Malfunction)
10 to 55 to 10 Hz 0.5-mm single amplitude (1.0-mm double amplitude) in each direction
Shock resistance (Destruction)
200 m/s**2 each direction 3 times (No defect in appearance and construction after applying shock in each directions 3 times.)
Shock resistance (Malfunction)
200 m/s**2
Endurance (Mechanical)
50000000 operations Min.
Endurance (Electrical)
50000 operations Min.
Protective structure
Closed type (cover)
Applicable standard (UL)
Standard No.: UL508
File No.: E41643Applicable standard (CSA)
Standard No.: C22.2 No.14
File No.: LR35535Terminal structure
Plug-in
Weight
Approx. 17 g
No comment |