No comment |
>
Control System >
VFD >
Delta VFD >
Delta Inverter VFD drive VFD037C43A 3Phase 380V 3.7KW 5HP 0~600Hz water pump &Machine toolVFD037C43A
Introduction
The C2000 series AC motor drive provides the most efficient and cost-effective solution for all types of drive applications. It features precise speed, torque and position control functions that are suitable for both sensor and sensorless types of synchronous and asynchronous motors. The C2000 series is also equipped with built-in PLC functions and supports the CANopen Master/Slave extension for the ultimate in system flexibility and fast data exchange.
Features
1. Replaces traditional brake resistor to reduce heat energy.
2. Clear energy saving: more than 95% of the regenerative energy is converted into electricity and supplied back to the mains.
3. Full-load operation : input-side current THD lower than 5% and improves power factor up to 99%.
4. AC motor drives with AFE2000: supports 4-quadrant operation with variable frequencies and adjustable system.
5. Constant DC bus voltage: unaffected by mains voltage fluctuations.
Applications
1. Large-inertia load, such as centrifuge equipment, dewatering machines and roving machines.
2. 4-quadrant loads including elevators, cranes and pumpjacks (oil extraction machines)
3. Quick braking, such as machine tools, bag making machines, auto storage and retrieval systems, and lathes.
4. Long-term energy feedback, such as wind power, water power, steel printing and paper making machinery (winding equipment).
5. Improves power quality for industries such as semiconductor and panel industries.
Specifications
230V
Frame Size
A
B
C
D
E
F
Model VFD-xxxCxx
007
015
022
037
055
075
110
150
185
220
300
370
450
550
750
900
Applicable Motor Output (kW)
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Applicable Motor Output(HP)
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
Output Rating
Normal
Duty
Rated Output Capacity(kVA)
2.0
3.2
4.4
6.8
10
13
20
26
30
36
48
58
72
86
102
138
Rated Output Current(A)
5
8
11
17
25
33
49
65
75
90
120
146
180
215
255
346
Overload Capacity
Rated Output Current: 120% for 1 minute
Max. Output Frequency(Hz)
0.00~600.00Hz
Carrier Frequency(kHz)
2~15kHz(8kHz)
2~10kHz(6kHz)
2~9kHz(4kHz)
Heavy Duty
Rated Output Capacity(kVA)
1.9
2.8
4.0
6.4
9.6
12
19
25
28
34
45
55
38
81
96
131
Rated Output Current(A)
4.8
7.1
10
16
24
31
47
32
71
86
114
139
171
204
242
329
Overload Capacity
Rated Output Current: 150% for 1 minute
Max. Output Frequency(Hz)
0.00~300.00Hz
Carrier Frequency(kHz)
2~6KHz(2kHz)
Input Rating
Input Current(A) Normal Duty
6.4
12
16
20
28
36
52
72
83
99
124
143
171
206
245
331
Input Current(A) Heavy Duty
6.1
11
15
18.5
26
34
50
68
78
95
118
136
162
196
233
315
Rated Voltage/Frequency
3-phase AC 200V~240V (-15%~+10%), 50/60Hz
Operating Voltage Range
170~265VAC
Frequency Tolerance
47~63Hz
Drive Weight
2.6+-0.3kg
5.4+-1kg
9.8+-1.5kg
38.5+-1.5kg
64.8+-1.5kg
86.5+-1.5kg
Cooling Method
Natural cooling
Fan cooling
Braking Chopper
Frame A, B, C: built in
Frame D and above: optional
DC choke
Frame A, B, C: optional
Frame D and above: built in
EMI Filter
Optional external EMI filter is available upon purchase
EMC-COP01
VFDxxxC23A: optional ; VFDxxxC23E: built in
460V Series
Frame Size
A
B
C
Model VFD-xxxCxx
007
015
022
037
040
055
075
110
150
185
200
300
Applicable Motor Output(kW)
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11
15
18.5
22
30
Applicable Motor Output(HP)
1
2
3
5
5
7.5
10
15
20
25
30
40
Output Rating
Normal Duty
Rated Output Capacity (kVA)
2.4
3.2
4.8
7.2
8.4
10
14
19
25
30
36
48
Rated Output Current(A)
3.0
4.0
6.0
9.0
10.5
12
18
24
32
38
45
60
Overload Capacity
Rated output current: 120% for 1 minute
Max output Frequency(Hz)
0.00~600.00Hz
Carrier Frequency(kHz)
2~15kHz(8kHz)
2~10kHz
Heavy Duty
Rated Output Capacity (kVA)
2.3
3.0
4.5
6.5
7.6
9.6
14
18
24
29
34
45
Rated Output Current(A)
2.9
3.8
5.7
8.1
9.5
11
17
23
30
36
43
57
Overload Capacity
Rated output current: 150% for 1 minute
Max output Frequency(Hz)
0.00~300.00Hz
Carrier Frequency(kHz)
2~6kHz(2kHz)
Input Rating
Input Current (A) Normal Duty
4.3
5.9
8.7
14
15.5
17
20
26
35
40
47
63
Input Current (A) Heavy Duty
4.1
5.6
8.3
13
14.5
16
19
25
33
38
45
60
Rated Voltage/Frequency
3-phase AC 380V-480V (-15%~+10%), 50/60Hz
Operating Voltage Range
323~528Vac
Frequency Tolerance
47~63Hz
Drive Weight
2.6+-0.3Kg
5.4+-1Kg
9.8+-1.5Kg
Cooling Method
Natural Cooling
Fan Cooling
Braking Chopper
Frame A. B, C : built in; Frame D and above: optional
DC choke
Frame A. B, C : optional; Frame D and above: built in
EMI Filter
Frame A, B, C VFDxxxC43E: built-in EMI filter
Frame A, B, C VFDxxxC43A : no EMI filter(Optional external EMI filter is available upon purchase)
EMC-COP01
VFDxxxC43A: optional; VFDxxC43E: built in
Dimensions
Wiring
No comment |