Your Position: Home > Control System > VFD > ABB VFD Drive > ACS510-01-072A-4 ABB Inverter New in box

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

ACS510-01-072A-4 ABB Inverter New in box

prevnext

ACS510-01-072A-4 ABB Inverter New in box
  • Market price: $ 6900.3
  • Shop price: $ 2091.0
  • Goods click count: 404
  • Total:
  • Quantity:
Add to cart collect
  

Description

ACS510-01-072A-4 ABB Inverter New in box

Product Description:

ABB standard drives are simple to buy, install, confgure and use, saving considerable time. They are widely available through ABB channel partners, hence the use of the term standard. The drives have common user and process interfaces with feldbuses, common software tools for sizing, commissioning, maintenance and common spare parts.

ABB standard drives can be used in a wide range of industries. Typical applications include pump, fan and constant torque use, such as conveyors. ABB standard drives are ideal in those situations where there is a need for simplicity to install, commission and use and where customizing or special product engineering is not required.

Features:

Ratings

Type code

Frame
size

SN
kVA

PN
kW

I N
A

2.3

1.1

3.3

ACS510-01-03A3-4

R1

3

1.5

4.1

ACS510-01-04A1-4

R1

4

2.2

5.6

ACS510-01-05A6-4

R1

5

3

7.2

ACS510-01-07A2-4

R1

6

4

9.4

ACS510-01-09A4-4

R1

9

5.5

11.9

ACS510-01-012A-4

R1

11

7.5

17

ACS510-01-017A-4

R2

16

11

25

ACS510-01-025A-4

R2

20

15

31

ACS510-01-031A-4

R3

25

18.5

38

ACS510-01-038A-4

R3

30

22

46

ACS510-01-046A-4

R3

41

30

60

ACS510-01-060A-4

R4

50

37

72

ACS510-01-072A-4

R4

60

45

88

ACS510-01-088A-4

R4

70

55

125

ACS510-01-125A-4

R5

100

75

157

ACS510-01-157A-4

R6

120

90

180

ACS510-01-180A-4

R6

140

110

205

ACS510-01-195A-4

R6

170

132

245

ACS510-01-246A-4

R6

200

160

290

ACS510-01-290A-4

R6

Notes: 1. SN kVA = Typical motor apparent output power in 400 V at normal use

2. PN kW = Typical motor power in 400 V at normal use

Frame
size 

 Dimensions and weights 

 IP1 / UL type 1 

 IP54 / UL type 1 

 H1mm 

 H2mm 

 Wmm 

 Dmm 

 Weight kg 

 Hmm 

 Wmm 

 Dmm 

 Weight kg 

 R1 

 369 

 330 

125

212

6.5

449

213

234

8.2

 R2

 469 

 430 

125

222

9

549

213

245

11.2

 R3 

 583 

 490 

203

231

16

611

257

253

18.5

 R4 

 689 

 596 

203

262

24

742

257

284

26.5

 R5 

 739 

602

265

286

34

776

369

309

38.5

 R6 

 880 

 700 

300

400

69

924

410

423

80

 R6

 986 

 700 

302

400

73

1119

410

423

84

Notes: H1 = Height with cable connection box H2 = Height without cable connection box  W = Width D = Depth

Mains connection

Programmable control connections

 Voltage and power range 

 3-phase, 380 to 480 V, +10/-15%, 1.1 - 160 kWAuto-identification of input line 

 Two analog inputs

 Frequency 

 48 to 63 Hz 

Voltage signal

 0 () to 10 V, Rin > 31 k¦¸single-ended 

 Power factor 

 0.98 

Current signal

0 (4) to 0 mA, Rin = 100¦¸single-ended10 V

Motor connection

Potentiometer reference value

 ±% max. 10 mA, R < 10 kΩ

 Voltage 

 3-phase, from 0 to USUPPLY 

Maximum delay

 1 to 3 ms

 Frequency 

 0 to 500 Hz(0 to 50HZ for N688, 0 to 55HZ for N689) 

Resolution 

0.10%

 Continuous loading capability(constant torque at a max ambient temperature of 400C) 

 Rated output current I 

Accuracy 

±1%

 Overload capacity(at a max. ambient temperature of 400C) 

 At normal use 1.1 x IN for 1 minute every 10minutes . 

 Two analog outputs 

 0 (4) to 0 mA, load < 500¦¸ 

 Switching frequencyStandard Selectable 

 Default 4 kHz 1 kHz, 4 kHz, 8 kHz, 1 kHz 

 Accuracy 

 ±3% 

 Acceleration time 

 0.1 to 1800 s 

 Auxiliary voltage 

 24 V DC ±10%, max 50 mA 

 Deceleration time 

 0.1 to 1800 s 

 Six digital inputs

 1 V... 4 V DC with internal or external supply, .

Environmental limits

Input impedance

PNP and NPN

 Ambient temperature-15 to 40oC40 to 50oC 

 No frost allowedSwitch frequency 4 kHz, derating please contact supplier 

Maximum delay 

2.4 kΩ 5 ms ± 1 ms 

 Altitude

 Rated current available at 0 to 1000 m

 Three relay outputs

 

Output current 

reduced by 1% per 100 m over 1000 m to 000 m 

Maximum switching voltage

 250 V AC/30 V DC 

 Relative humidity 

 lower than 95% (without condensation)  

Maximum switching current

6 A/30 V DC; 1500 V A/30 V AC

 Protection class 

 IP1 or IP54 

Maximum continuous current 

  2 A rms 

 Enclosure colour 

 NCS 150-Y, RAL 900, PMS 40 C 

 Serial communicationRS 485 

 Modbus protocol 

 Contamination levels 

 IEC 71-3-3 No conductive dust allowed   

Protection limits

Transportation

Class 1C2 (chemical gases), Class 1S2 (solid particles)

Overvoltage trip limits

Storage

Class 2C2 (chemical gases), Class 2S2 (solid particles)

 Running V DC

 84 (corr. to 595 V input) 

Operation

Class 3C2 (chemical gases), Class 3S2 (solid particles) 

Start inhibit V DC 

661 (corr. to 380 - 415 V input), 

 

 

Undervoltage trip

 

 

Running V DC

 333 (corr.to 47 V input) 

 

 

Start inhibit V DC 

436 (corr.to  380 - 415 V input), 






  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: