No comment |
>
Control System >
VFD >
ABB VFD Drive >
ACS510-01-038A-4 ABB Inverter New in boxACS510-01-038A-4 ABB Inverter New in boxProduct Description:
ABB standard drives are simple to buy, install, confgure and use, saving considerable time. They are widely available through ABB channel partners, hence the use of the term standard. The drives have common user and process interfaces with feldbuses, common software tools for sizing, commissioning, maintenance and common spare parts.
ABB standard drives can be used in a wide range of industries. Typical applications include pump, fan and constant torque use, such as conveyors. ABB standard drives are ideal in those situations where there is a need for simplicity to install, commission and use and where customizing or special product engineering is not required.
Features:
Ratings
Type code
Frame
sizeSN
kVAPN
kWI N
A2.3
1.1
3.3
ACS510-01-03A3-4
R1
3
1.5
4.1
ACS510-01-04A1-4
R1
4
2.2
5.6
ACS510-01-05A6-4
R1
5
3
7.2
ACS510-01-07A2-4
R1
6
4
9.4
ACS510-01-09A4-4
R1
9
5.5
11.9
ACS510-01-012A-4
R1
11
7.5
17
ACS510-01-017A-4
R2
16
11
25
ACS510-01-025A-4
R2
20
15
31
ACS510-01-031A-4
R3
25
18.5
38
ACS510-01-038A-4
R3
30
22
46
ACS510-01-046A-4
R3
41
30
60
ACS510-01-060A-4
R4
50
37
72
ACS510-01-072A-4
R4
60
45
88
ACS510-01-088A-4
R4
70
55
125
ACS510-01-125A-4
R5
100
75
157
ACS510-01-157A-4
R6
120
90
180
ACS510-01-180A-4
R6
140
110
205
ACS510-01-195A-4
R6
170
132
245
ACS510-01-246A-4
R6
200
160
290
ACS510-01-290A-4
R6
Notes: 1. SN kVA = Typical motor apparent output power in 400 V at normal use
2. PN kW = Typical motor power in 400 V at normal use
Frame
sizeDimensions and weights
IP1 / UL type 1
IP54 / UL type 1
H1mm
H2mm
Wmm
Dmm
Weight kg
Hmm
Wmm
Dmm
Weight kg
R1
369
330
125
212
6.5
449
213
234
8.2
R2
469
430
125
222
9
549
213
245
11.2
R3
583
490
203
231
16
611
257
253
18.5
R4
689
596
203
262
24
742
257
284
26.5
R5
739
602
265
286
34
776
369
309
38.5
R6
880
700
300
400
69
924
410
423
80
R6
986
700
302
400
73
1119
410
423
84
Notes: H1 = Height with cable connection box H2 = Height without cable connection box W = Width D = Depth
Mains connection
Programmable control connections
Voltage and power range
3-phase, 380 to 480 V, +10/-15%, 1.1 - 160 kWAuto-identification of input line
Two analog inputs
Frequency
48 to 63 Hz
Voltage signal
0 () to 10 V, Rin > 31 k¦¸single-ended
Power factor
0.98
Current signal
0 (4) to 0 mA, Rin = 100¦¸single-ended10 V
Motor connection
Potentiometer reference value
±% max. 10 mA, R < 10 kΩ
Voltage
3-phase, from 0 to USUPPLY
Maximum delay
1 to 3 ms
Frequency
0 to 500 Hz(0 to 50HZ for N688, 0 to 55HZ for N689)
Resolution
0.10%
Continuous loading capability(constant torque at a max ambient temperature of 400C)
Rated output current I
Accuracy
±1%
Overload capacity(at a max. ambient temperature of 400C)
At normal use 1.1 x IN for 1 minute every 10minutes .
Two analog outputs
0 (4) to 0 mA, load < 500¦¸
Switching frequencyStandard Selectable
Default 4 kHz 1 kHz, 4 kHz, 8 kHz, 1 kHz
Accuracy
±3%
Acceleration time
0.1 to 1800 s
Auxiliary voltage
24 V DC ±10%, max 50 mA
Deceleration time
0.1 to 1800 s
Six digital inputs
1 V... 4 V DC with internal or external supply, .
Environmental limits
Input impedance
PNP and NPN
Ambient temperature-15 to 40oC40 to 50oC
No frost allowedSwitch frequency 4 kHz, derating please contact supplier
Maximum delay
2.4 kΩ 5 ms ± 1 ms
Altitude
Rated current available at 0 to 1000 m
Three relay outputs
Output current
reduced by 1% per 100 m over 1000 m to 000 m
Maximum switching voltage
250 V AC/30 V DC
Relative humidity
lower than 95% (without condensation)
Maximum switching current
6 A/30 V DC; 1500 V A/30 V AC
Protection class
IP1 or IP54
Maximum continuous current
2 A rms
Enclosure colour
NCS 150-Y, RAL 900, PMS 40 C
Serial communicationRS 485
Modbus protocol
Contamination levels
IEC 71-3-3 No conductive dust allowed
Protection limits
Transportation
Class 1C2 (chemical gases), Class 1S2 (solid particles)
Overvoltage trip limits
Storage
Class 2C2 (chemical gases), Class 2S2 (solid particles)
Running V DC
84 (corr. to 595 V input)
Operation
Class 3C2 (chemical gases), Class 3S2 (solid particles)
Start inhibit V DC
661 (corr. to 380 - 415 V input),
Undervoltage trip
Running V DC
333 (corr.to 47 V input)
Start inhibit V DC
436 (corr.to 380 - 415 V input),