No comment |
>
Control System >
PLC >
Other PLC >
LX1S-14MR-A WECON PLC 100-240VAC 8 point 24V relay 6 point 1 COM Original brand newLX1S-14MR-A WECON PLC 100-240VAC 8 point 24V relay 6 point 1 COM Original brand new
Description
Power specifications
Rated voltage
AC100-240V
Allowed limits
AC85-264V
Rated frequency
50/60HZ
Allowed instant outage time
Instant outage time less than 10 ms,can continue to work.
power fuse
250V 1A
Power consumption
Maximum 15A 5ms below/AC 100V,Maximum 5ms below/AC200V
Power consumption
Less than 20W
Sensor power
DC24V 400mA
General Specifications
Environment temperature
0 ~ 55 ?
Storage temperature
-20 ~ 70?
Relative humidity
35-85%RH
Seismic resistance
(DIN rails)
Meet JIS C 0040 standards, 10-57HZ 0.035MM X,Y,Z three direction 10 times each(total 80 minute each)
Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X,Y,Z three direction,10 times each,(total 80 minute each)
Seismic resistance
(install directly)
Meet JIS C 0040 standards, 10-57HZ 0.035MM X.Y.Z three direction ,10 times each(total 80 minute each)
Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X.Y.Z three direction,10 times each,( total 80 minute each)
Impact Resistance
Meet JIS C 0040 standard(147m/S2 action time, 11ms half-sine shock pulse,in X,Y,Z three direction,3 times each)
Noise resistance
Noise voltage 1,000VP-P noise amplitude 1ns 1 frequency 30 ~ 100HZ noise simulation experiment
Withstand Voltage
AC1500V(1 minute),meet JEM-1021 standards,between power port and earth terminal.
Insulation resistance
DC500V insulation tester test above 5MΩ, meet JEM-1021 standards,between power port and earth terminal.
Earth connection
The third kind of earth connection(do not share one place with high voltage system) ?1
Operating environment
Close corrosive,combustible gas, No large electrical conductivity dust
Instruction specifications
Shell color
black
Shell material
ABS Plastic
Shape Size
90×75×75mm
Package size
137*102*97mm
Net weight
0.3kg
Wet weight
0.5kg
No comment |