Features:
XGB, which is a micro PLC that offers maximum automation value at minimum cost, Is capable of handling most tasks from simple to complex control with high performance and functionality. (XEC: IEC Standard Programming)
Compactness & High Performance
*XGB is more compact but provides powerful functions and performance.
*Compact & Powerful solutions & XGB’s steadfast competitiveness.
Easiness & Convenience
XGB offers convenient user interface with various network diagnosis & monitoring functions and back-up function
*Integrated programming environment
-Enhanced user interface with XG5000/XG-PD
-Various monitoring functions.
-Network diagnosis and monitoring
*Optimum communication environment
-Powerful communications: Built-in RS-232C/485, 2 Expansions for communication
-Network configuration via Ethernet and Cnet I/F
Analog Product List:
Classification
Name
No. of
channel
Range
Resolution
Characteristic
Voltage/Current
input
XBF-AD04A
4
0 ~ 10V
2.5 mV
1.Range selection by external switch and
parameter setting
2. External DC24V used
0~20mA
4mA~20mA
5.0 μA
XBF-AD08A
8
4~20mA
0~20mA
5.0 μA
1.Range selection by external switch and
parameter setting
2. Filter function, average function
3. External DC24V used
1~5V
0~5V
1.25 mV
0~10V
2.5 mV
Specifications:
Item
XBF-AD08A
Analog input
range
Type
Voltage
Current
Range
DC 1 ~ 5V
DC 0 ~ 5V
DC 0 ~ 10V
(Input resistance: 1 MΩ min.)
DC 4 ~ 20mA
DC 0 ~ 20mA
(Input resistance: 250 Ω)
Input range can be voltage/current selector switch after being set
by user program or I/O parameter for each channel
Digital output
Type
12 bit binary data
Range
Unsigned value
0 ~ 4000
Signed value
-2000 ~ 2000
Precise value
100 ~ 500 (DC 1 ~ 5V)
0 ~ 500 (DC 0 ~ 5V)
0 ~ 1000 (DC 0 ~ 10V)
400 ~ 2000 (DC 4 ~ 20mA)
0 ~ 2000 (DC 0 ~ 20mA)
Percentile value
0 ~ 1000
Max. resolution
1/4000
1.25mV (DC 1~5V, 0~5V)
2.5mV (DC 0~10V)
5uA (DC4~20mA, 0~20mA)
Accuracy
± 0.5% or less
Max. conversion speed
1.5ms/channel
Absolute max. input
DC ±15V
DC +25mA
No. of output channel
4 channels
Insulation method
Photo-coupler insulation between input terminal and PLC power (No insulation between channels)
Connection Terminal
11 point terminal block
I/O points occupied
Fixed type: 64 points
Max. number of equipment
7 (when using XBM(C)-DxxxS “S”type)
10 (when using XB(E)C-DxxxH “H”type)
Additional
function
Filter function
Digital filter (4~64,000ms)
Average function
Time average (4~16,000ms)
Count average (2~64,000 times)
Moving average (2~100)
Alarm function
Disconnection detection (DC 1~5V, DC 4~20mA)
Consumption
current
Inner (DC 5V)
105mA
External (DC 24V)
85mA
Weight (g)
81