No comment |
>
Control System >
PLC >
Other PLC >
XBC-DN30SU LS PLC XGB Series Standard Type 18-point DC Input 12-point Transistor Output AC100~240V NewXBC-DN30SU LS PLC XGB Series Standard Type 18-point DC Input 12-point Transistor Output AC100~240V NewPLCAGE: XBC-DN30SU LS(LG) PLC XGB Series Standard Type 18-point DC Input 12-point Transistor Output AC100~240V New
Features:
XBC/XEC: Terminal block type
*Supporting floating-point arithmetic
*Built-in Cnet, HSC, PID, Positioning, Pulse catch, Input filter, External Interrupt
*Expansion Cnet, Ethernet
*Download port: Serial, USB
XBC/XEC
*Economic type
- CPU processing speed: 240ns/step
- Max 38 I/O points
- Program capacity: 4Ksteps
*Standard type
- CPU processing speed: 94ns/step
- Max. 284 I/O points
- Program capacity: 15Ksteps/200KB(XBC/XEC)
*High performance type
- CPU processing speed: 83ns/step
- Max. 384 I/O points
- Program capacity: 15Ksteps/200KB(XBC/XEC)
Specifications:
Items
Specifications (“S” type)
Remark
XBC-DN20S
XBC-DR20S
XBC-DN30S
XBC-DR30S
Program control method
Reiterative operation, fixed cycle operation, constant scan
I/O control method
Scan synchronous batch processing method (Refresh method),
Directed by program instruction
Program language
Ladder Diagram, Instruction List
Number of
instructions
Basic
28
Application
687
Processing speed
(Basic instruction)
94 ns/Step
Program capacity
15 k steps
Max. I/O points
244 point (Main + Expansion 7 stages)
254 point (Main + Expansion 7 stages)
Data area
P
P0000 ~ P1023F (16,384 point)
M
M0000 ~ M1023F (16,384 point)
K
K0000 ~ K4095F (65,536 point)
L
L0000 ~ L2047F (32,768 point)
F
F0000 ~ F1023F (16,384 point)
T
100ms, 10ms, 1ms : T0000 ~ T1023 (1,024 point)
(Adjustable by parameter setting)
C
C0000 ~ C1023 (1,024)
S
S00.00 ~ S127.99
D
D0000 ~ D10239 (10,240 word)
Word
U
U00.00 ~ U0A.31 (Analog data refresh area: 352 word)
Z
Z000~Z127 (128 Word)
R
R0000~R10239 (10,240 word)
Total program
128
Initial task
1
Cyclic task
Max. 8
I/O task
Max. 8
Internal device task
Max. 8
Operation mode
RUN, STOP, DEBUG
Self-diagnosis function
Detects errors of scan time, memory, I/O
Program port
RS-232C 1 channel
Back-up method
Latch area setting in basic parameter
Internal consumption current
240 mA
255 mA
Weight(g)
470
475
No comment |