No comment |
>
Control System >
PLC >
Other PLC >
PLC AC100-220V 16 DI 12 DO relay Main Unit VIGOR VH-28MR NewVH-28MR PLC VIGOR 24VDC 16 point 24VDC relay 12 point Main Unit Original brand new
Functional specification
Item
Specifications
Operation Control Method
Cyclic Operation by Stored Program
Programming Language
Electric Ladder Diagram + SFC
1/0 Control Method
Batch Processing
Operation
Processing Time
Basic Instruction
0.375 -12.56J1S
Applied Instruction
Several JlS- Several100 flS
Memory Capacity (Flash ROM)
Program Capacity
Built-in 4 K Steps Flash ROM
Comment Capacity
2730 comments (16 characters or 8 Chinese characters for each comment)
Program Comment Capacity
20,000 characters or 10,000 Chinese characters
Max. Input I Output Points
128 points: XO-X77, YO- Y77
Internal
Relay
Auxiliary Coil
(M)
General
384 points: MO- M383
Latched
128 points: M384- M511
Special
256 points: M9000- M9255
State Coil
(S)
Initial
10 points: SO- S9 (Latched)
Latched
118 points: S10 -S127
Timer
(T)
100mS
63 points: TO- T62 (Timer range: 0.1-3276.7 sec.)
10mS
31 points: T32- T62 (Timer range: 0.01-327.67 sec.), when the coil M9028= "ON"
1 ms
1 points: T63 (Timer range: 0.001 - 32.767 sec.)
Counter
(C)
16-bit U
General
16 points: CO- C15
Latched
16points: C16-C31
High Speed
Counter (C)
32-bit Up/Down
1-phase Counter
11 points: C235 - C245 (Signal Frequency: 10KHz Max.)
2-phase Counter
5 points: C246- C250 (Signal Frequency: 10 KHz Max.)
A/B Phase Counter
4 points: C251 - C254 (Signal Frequency: 5 KHz Max.)
Data Register
(D)
General
128 points: DO- D127
Latched
128 points: D128- D255
Special
256 points: D9000 - D9255
Index
16 points: VO- V7, ZO- Z7
Level
Branch Level (P)
64 points: PO - P63
Interrupt Level (I)
15 points: 6 points for external interrupt, 3 points for timer interrupt, and 6 points for counter interrupt
Nest Level (N)
8 points: NO- N7
Constants
Decimal
(K)
16 Bits
-32768 - 32767
32 Bits
-2147483648-2147483647
Hexadecimal
(H)
16 Bits
OH- FFFFH
32 Bits
OH- FFFFFFFFH
Pulse Output
1 point; Max. 7 KHz
Programming Device Link Interface CP1
RS-232C, available direct connect to a computer, HMI or MODEM
Communication Link Interface CP2 (Optional)
RS-232C or RS-422 I RS-485, available direct connect to a computer, HMI or MODEM
Communication Link Interface CP3 (Optional)
RS-485, available direct connect to a computer, HMI
Real Time Clock (Optional)
To indicates year, month, day, hour, min., sec. and week
Error Code Display Function
Displays 109 error codes (01-99 and EO-E9)
Analog Potentiometer
2 Analog Potentiometers, each one can be seating as 0255