Your Position: Home > Control System > PLC > Panasonic PLC > FP-X0 L60R AFPX0L60R Panasonic PLC 100-240VDC DC input 32 points Relay output 24 points FP-X0 Control Unit Original New

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

FP-X0 L60R AFPX0L60R Panasonic PLC 100-240VDC DC input 32 points Relay output 24 points FP-X0 Control Unit Original New

prevnext

FP-X0 L60R AFPX0L60R Panasonic PLC 100-240VDC DC input 32 points Relay output 24 points FP-X0 Control Unit Original New
  • Market price: $ 966.9
  • Shop price: $ 293.0
  • Goods click count: 408
  • Total:
  • Quantity:
Add to cart collect
  

Description

FP-X0 L60R AFPX0L60R Panasonic PLC 100-240VDC DC input 32 points Relay output 24 points FP-X0 Control Unit Original New


Feature

Super-high Processing Speed

Super-high speed of 80 ns/step for 0 to 3000 steps (ST command).

580 ns/step processing speed for 3001 steps or more (Only for L40 and L60).

Program Memory

L14 and L30: 2.5 k steps
L40 and L60: 8 k steps

The Maximum Number of I/O Points

One control unit can be connected with up to 3 expansion units. Therefore, the maximum number can reach 150 points.
In addition, if the expansion FP0 adaptor is used, the maximum number can reach 216 points when the FP0R expansion unit is used. (Only for L40R, L40MR, L60R and L60MR)

Performance specifications

Items

Specifications

L14R

L30R

L40R

L40MR

L60R

L60MR

Controllable I/O points

Control unit

DC input
8 points,
Relay
output
4 points,
Transistor
output
2 points

DC input
16 points,
Relay
output
10 points,
Transistor
output
4 points

DC input 24 points,
Relay output 12
points,
Transistor output 4
points

DC input 32 points,
Relay output 24
points,
Transistor output 4
points

When using FP-X E16
expansion I/O units

-

-

88 points max.
(3 expansion units
max.)

108 points max.

When using FP-X E30
expansion I/O units

-

-

130 points max.
(3 expansion units
max.)

150 points max.
(3 expansion units
max.)

When using FP0R
expansion units

-

-

196 points max.
(3 expansion units
max.)

216 points max.
(3 expansion units
max.)

Programming method/Control method

Relay symbol/Cyclic operation

Program memory

Built-in Flash-ROM (Free of backup battery)

Program capacity

2.5 k steps

8 k steps

No of
instruction

Basic commands

Approx. 114 kinds

High-level commands

Approx. 230 kinds

Processing speed

0.08 µs/step for basic
commands
0.32 µs for high-level
commands
(MV commands)

3 k steps: 0.08 µs/step for basic commands, 0.32 µs
for high-level commands(MV commands)
After 3 k steps: 0.58 µs/step for basic commands,
1.62 µs for high-level commands(MV
commands)

I/O refreshing + basic time

Basic time

0.15 ms or less

0.18 ms or less

0.31 to 0.35 ms or less

0.34 to 0.39 ms or less

 

When using E16: 0.4 ms × No. of units
When using E30: 0.5 ms × No. of units
When using FP0 expansion adaptors: 1.4 ms + the refreshing
time of the FP0 expansion unit

Memory for processing

Relays

External input (X) (Note 1)

960 points

1760 points

External output (Y) (Note 1)

960 points

1760 points

Internal relay (R)

1008 points

4096 points

Special internal relay (R)

224 points

Timer Counter (T/C)

256 points (Note 2)

1024 points (Note 2)

Timer: (1 ms, 10 ms, 100 ms, 1 s)× 32767, Counter: 1 to 32767

Link relay (L)

No

2048 points

Memory area

Data register (DT)

2500 words

8192 words

Special data register (DT)

420 words

Link data register (LD)

No

256 words

File registration (FL)

No

Index register (I)

14 words (IO to ID)

Differential points

Equivalent to program capacity

Master control relay (MCR)

32 points

256 points

Label number (JP+LOOP)

100 points

256 points

No. of step programs

128 (Engineering)

1000 (Engineering)

No. of subroutines

100

500

No. of interrupt programs

Input: 8 programs, timing: 1 program

Sampling trace

No

Yes

Comments storage

All of the I/O comments,explanations and block comments can
be saved.(Free of backup battery, 328 k bytes)

PLC link function

No

Yes

Constant scan

In unit of 0.5 ms: 0.5 ms to 600 ms

Password

Available (4 or 8 digits)

Upload protection

Available

Self-diagnosis function

Checks of the watchdog timer and the program syntax

Program editting during
Run

Available (Capacity modified simultaneously: 128 steps)
But comments cannot be modified during the process.

Available (Capacity modified simultaneously: 512 steps)
But comments can be modified during the process.

Downloading during Run

Available

High-speed
counter
(Note 3) (Note 4)

Body input

1-phase, 4-channel
(20 kHz max.)
and 2-phase, 2-channel
(20 kHz max.)

1-phase, 4-channel (50 kHz max.)
and
2-phase, 2-channel (20 kHz max.)

Pulse output/
PWM output
(Note 3) (Note 4)

Body output

Pulse:
1-channel
(20 kHz max.)
PWM:
1-channel
(1.6 kHz max.)

Pulse:
2-channel
(20 kHz max.)
PWM:
2-channel
(1.6 kHz max.)

Pulse: 2-channel (50 kHz)
PWM: 2-channel(3.0 kHz max.)

Pulse catch input/
Interrupt program

8 points
(High-speed counting and interrupt input included)

Analog input

No

2-channel (For inputting any of the
following items in each channel)

Potentiometer input
Min. resistance value of potentiometer:
5 kΩ
10-bit resolution (K0 to K1000)
Accuracy ± 1.0% F.S.+ accuracy of
external reistors

Thermistor input
For inputting the resistance value of the
thermistor
(Min. resistance value of external
thermistors + external resistance value
> 2 kΩ)
10-bit resolution (K0 to K1023)
Accuracy ± 1.0% F.S.+ accuracy of
external thermistors

Voltage input
Absolute max. input voltage: 10 V
10-bit resolution (K0 to K1023)
Accuracy ± 2.5% F.S.(F.S. = 10 V)

Calendar/clock

No

Yes

Flash ROM
backup
(Note 5)

Backup made
according to
commands of
F12 and P13

Data memory
(2500 words)

Data memory
(8192 words)

Automatic
backup when
power OFF

Counter: 6 points
(C250 to C255)
Process value of the
counter: 6 points
(EV250 to EV255)
Internal relays: 5 points
(WR58 to WR62)
Data memory: 300 words
(DT2200 to DT2499)

Counter: 16 points (C1008 to C1023)
Process value of the counter: 16 points
(EV1008 to EV1023)
Internal relays: 8 points
(WR248 to WR255)
Data memory: 302 words
(DT7890 to DT8191)

Backup battery

No

Yes (Backup lasting for the whole process)

RS485 communication port

No

Yes

No

Yes

Note 1) The actual usable points depend on the combination of the hardware.
Note 2) The points of the timer can be added as required.
Note 3) The rated voltage is 24 V DC at 250C. The frequency may fall according to the changes of the voltage, temperature and operating conditions.
Note 4) The maximum frequency may vary with the difference of the operating method.
Note 5) The allowable writing operation is within 10000 times. Areas to be held and not held can be specified using the system registers.

Dimension Figure

  













































  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: