No comment |
FX2N-5A Mit PLC 4 AI 1 AO Module New
Introduction
The FX2N-5A analog special function block has four input channels and one output channel.
The input channels receive analog signals and converts them to the comparable digital values.
The output channel takes a digital value and outputs an equivalent analog signal.
1, Analog signal inputs can be selected from either voltage or current input. The applicable analog signal input is set using the TO instruction supplied by the PLC main unit.
This PLC instrution is used to select different analog input signal types for each corresponding channel.
2,The FX2N-5A can be connected to FX0N/FX1N/FX2N/FX2NC/FX3G/FX33GC/FX3U/FX3UC series PLC
3, Up to 2 FX2N-5A units can be connected to FX0N main unit, FX0N extension unit, Fx1N ,main unit.
Power supply specifications
Item
Specifications
Interface driving power supply
24VDC+-10%, 90mA (maximum), externally Supplied
CPU driving power supply
5VDC, 70mA, supplied via extension cable from PLC main unit
Perfomance specifications
Item
specifications
Conversion Speed
Channel for voltage/current input: 1ms x Number of used channels
Channel for voltage/current output: 2ms (See BFM 25)
Insulation Method
Photocoupler insulates the annlog input/output area from PLC.
DC/DC converter insulates the power supply from analog I/O.
Channels are not insulated against each other
Number of occupied I/O points
8 points (including input and output points0
Applicable PLC
FX0N, FX1N. FX2N, FX2NC, FX3G, FX3GC, FX3U, FX3UC Series PLC
For connection to the FX2NC Series PLC, an FX2NC-CNV-IF is required.
For connection to the FX3GC/FX3UC Series PLC, an FX2NC-CNV-IF or FX3UC-1PS-5V is required
Built-in memory
EEPROM
External Dimensions and Parts