Your Position: Home > Control System > PLC > Mitsubishi PLC > FX3U-80MT-DS PLC 24V DC 40DI 40DO Transistor with Programing Cable Mitsubishi

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

FX3U-80MT-DS PLC 24V DC 40DI 40DO Transistor with Programing Cable Mitsubishi

prevnext

FX3U-80MT-DS PLC 24V DC 40DI 40DO Transistor with Programing Cable Mitsubishi
  • Market price: $ 1544.4
  • Shop price: $ 468.0
  • Goods click count: 257
  • Total:
  • Quantity:
Add to cart collect
  

Description

FX3U-80MT-DS Mitsubishi PLC Base Unit Original Brand NEW


General Specifications [Main Unit]

Item

Ambient

temperature

Ambient temperature

0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored

Ambient humidity

5 to 95%RH (no condensation) when operating

Vibration resistance

Conforms to EN 68-2-6

 

Frequency

(Hz)

Acceleration

(m/s

2

)

Half

amplitude

(mm)

Sweep Count

for X, Y, Z: 10

times

(80 min in

each direction)

When

installed

on DIN

rail

10 to 57

--

0.035

57 to 150

4.9

--

When

installed

directly

10 to 57

--

0.075

57 to 150

9.8

--

Shock resistance

Compliant with EN 68-2-27

(147 m/s2Acceleration, Action time: 11ms, 3 times by

half-sine pulse in each direction X, Y, and Z)

Noise resistance

By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of 30

to 100 Hz

Dielectric withstand voltage*1

 

1.5kV AC for one minute

Compliant with JEM-1021 Between each terminals*1 and ground terminal

500V AC for one minute

Insulation resistance*1

5MΩ or more by

500V DC megge

Grounding

Class D grounding (grounding resistance: 100  Ω or

less)

system is not allowed.>*2

Working atmosphere

Free from corrosive or flammable gas and excessive conductive dusts

Working altitude

Compliant with IEC61131-2 (<2000m)*3

       

*1

Terminal

Dielectric strength

Insulation resistance

Between power supply

terminal (AC power) and

ground terminal

1.5 kV AC for

one minute

5MΩ or more by

500V DC megger

Between power supply

terminal (DC power) and

ground terminal

500V AC for

one minute

Between input terminal

(24V DC) and ground

terminal

500V AC for

one minute

Between output terminal

(relay) and ground

terminal

1.5 kV AC for

one minute

Between output terminal

(transistor) and ground

terminal

500V AC for

one minute

For dielectric with stand voltage test and insulationresistance test of each product, refer to the following manual.

→ Refer to FX3U Series User's Manual - Hardware Edition.

*2 For common grounding, refer to section 3.3.

*3 The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.


  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: