Omron PLC CP1E-N30DR-A-CH New in boxProduct Description?
The CP1E all-in-one package PLCs provide high cost performance to further reduce costs by allowing you to select the optimal CPU Unit from the E-type Basic Models or N-type Application Models.
Specifications?
Type
AC power supply models
DC power supply models
Model
CP1E-[][][]D[]-A
CP1E-[][][]D[]-D
Enclosure
Mounted in a panel
Dimensions (H × D × W)
CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 90mm *1 ×85mm *2 × 66 mm
CPU Unit with 14 or 20 I/O points (CP1E-[]14D[]-[]/[]20D[]-[]): 90mm *1 × 85mm *2 × 86 mm
CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 90mm *1 × 85mm *2 × 130 mm
CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 90mm *1 × 85mm *2 × 150 mm
CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 90mm *1 ×85mm *2 × 195 mm
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 90mm *1 ×85mm *2 × 130 mmWeight
CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 300g max.
CPU Unit with 14 I/O points (CP1E-[]14D[]-[]): 360g max.
CPU Unit with 20 I/O points (CP1E-[]20D[]-[]): 370g max.
CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 600g max.
CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 660g max.
CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 850g max.
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 680g max.Electrical
specifica-
tionsSupply voltage
100 to 240 VAC 50/60 Hz
24 VDC
Operating voltage
range85 to 264 VAC
20.4 to 26.4 VDC
Power consumption
15 VA/100 VAC max.
25 VA/240 VAC max.
(CP1E-E10D[]-A/[]14D[]-A/[]20D[]-A)9 W max. (CP1E-E10D[]-D)
13 W max. (CP1E-N14D[]-D/N20D[]-D)50 VA/100 VAC max.
70 VA/240 VAC max.
(CP1E-NA20D[]-A/[]30D[]-A/[]40D[]-A/N60D[]-A)20 W max.
(CP1E-NA20D[]-D/N30D[]-D/N40D[]-D/N60D[]-D) *4Inrush current
120 VAC, 20 A for 8 ms max. for cold start at
room temperature
240 VAC, 40 A for 8 ms max. for cold start at
room temperature24 VDC, 30 A for 20 ms max. for cold start at room
temperatureExternal power supply
*3Not provided.
(CP1E-E10D[]-A/[]14D[]-A/[]20D[]-A)
24 VDC, 300 mA
(CP1E-NA20D[]-A/[]30D[]-A/[]40D[]-A/N60D[]-A)Not provided
Insulation resistance
20 MΩ min. (at 500 VDC) between the external
AC terminals and GR terminalsExcept between DC primary current and DC
secondary currentDielectric strength
2,300 VAC 50/60Hz for 1 min between AC
external and GR terminals Leakage current:
5 mA max.Except between DC primary current and DC
secondary currentPower OFF
detection time10 ms min.
2 ms min.
Application
environ-
mentAmbient operating
temperature0 to 55 °C
Ambient humidity
10% to 90%
Atmosphere
No corrosive gas.
Ambient storage
temperature-20 to 75 °C (excluding battery)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise resistance
2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage category
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level
Zone B
Vibration resistance
Conforms to JIS 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)Shock resistance
Conforms to JIS 60068-2-27.
147 m/s2, 3 times in X, Y, and Z directionsTerminal block
Fixed (not removable)
Terminal screw size
M3
Applicable standards
Conforms to EC Directive
Grounding method
Ground to 100 Ω or less.
*1.Total of 110 mm with mounting brackets.
*2.Excluding cables.
*3.Use the external power supply to power input devices. Do not use it to drive output devices.
*4.This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with DC power.
Formula: DC power consumption = (5V current consumption × 5 V/70% (internal power efficiency) + 24V current consumption) × 1.1(current fluctuation factor)
The above calculation results show that a DC power supply with a greater capacity is required.