No comment |
>
Control System >
PLC >
Omron PLC >
CJ1W-AD041-V1 PLC OMRON I/O 4 point input Original brand newCJ1W-AD041-V1 PLC OMRON I/O 4 point input Original brand new
Features
Analog Input Units
Input up to eight analog signals with one Unit.
Functions include line disconnection detection, averaging, peak value holding, offset/gain adjustment, and scaling. (Offset/gain adjustment is not supported by the CJ1W-AD042. Scaling is supported only by the CJ1W-AD042.)
High-speed A/D conversion in 20 μs/point with direct conversion function * (CJ1W-AD042 only).
Analog Output Units
Output up to eight analog signals with one Unit.
Functions include output holding, offset/gain adjustment, and scaling. (Offset/gain adjustment is not supported by the CJ1W-DA042V. Scaling is supported only by the CJ1W-DA08V/DA08C/DA042V.)
High-speed D/A conversion in 20 μs/point with direct conversion function * (CJ1W-DA042V only).
Analog I/O Units
Input up to four analog signals and output up to two analog signals with one Unit.
Functions include line disconnection detection, input averaging, scaling, input peak value holding, output holding, ratio conversion, and offset/gain adjustment.
* Direct Conversion Instructions for High-speed type can be used to create a consistent response time from input through
data processing and output. With the Machine Automation Controller NJ-series, the direct conversion function cannot be
used. This function is supported only by the CJ-series CPU Unit.Parameter specification
Product
nameI/O
pointsSignal
rangeResolution
Conversion
periodAccuracy at
ambient
temperature
of 25 °CCurrent
consump-
tion (A)Model
Standards
5 V
24 V
Analog
Input Unit
(High-speed
type)4
inputs1 to 5 V (1/10,000),
0 to 10 V (1/20,000),
-5 to 5 V (1/20,000),
-10 to 10 V (1/40,000),
and
4 to 20 mA (1/10,000)20 μs/1 point,
25 μs/2 points,
30 μs/3 points,
35 μs/4 points
The Direct
conversion is
provided. *1Voltage:
±0.2% of F.S.
Current:
±0.4% of F.S.0.52
---
CJ1W-AD042
UC1, CE
Analog
Input Units8
inputs1 to 5 V,
0 to 5 V,
0 to 10 V,
-10 to 10 V,
4 to 20 mA1/4,000
(Settable to
1/8,000)
*21 ms/point
(250 μs/point
can also be set.)
*2Voltage:
± 0.2% of F.S.
Current:
± 0.4% of F.S.
*30.42
---
CJ1W-AD081-V1
UC1, N, L,
CE4
inputsCJ1W-AD041-V1
Dimension