CJ1W-OD201 Omron PLC New in box

Omron PLC CJ1W-OD201

Product Description:

1. High-speed output models are available, meeting versatile applications.
2. ON Response Time: 15μs, OFF Response Time: 80μs

3. Output Units are available with any of three output types: relay contact outputs, triac outputs, or transistor outputs.

4. For transistor outputs, select from sinking outputs or sourcing outputs.

5. Output Units with load short-circuit protection are also available. *1

6. Select the best interface for each application: Fujitsu connectors or MIL connectors. *2

7. A wide variety of Connector-Terminal Block Conversion Units are available to allow you to easily wire external output devices.

*1.The following Units have load short-circuit protection: CJ1W-OC202, CJ1W-OD204, CJ1W-OD212, and CJ1W-OD232.

*2.Available for models with 32 outputs or 64 outputs

Features:? 

Name

8-point Transistor Output Unit with Terminal Block (Sinking Outputs)

Model

CJ1W-OD201

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

2.0 A/point, 8.0 A/Unit

Maximum Inrush Current

10 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10
mA max.

Number of Circuits

8 (4 points/common, 2 circuits)

Internal Current Consumption

90 mA max.

Fuse

6.3 A (1/common, 2 used)
The fuse cannot be replaced by the user.

External Power Supply

12 to 24 VDC, 10 mA min.

Weight

110 g max.

*Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units.




  