PLC 4 AO Module Delta DVP04DA-S Delta New
The communication cable, which connects Human Interface and PLC, isn’t provided for free. If needed, please inform us of your HMI model, we will offer a best price.
Delta PLC programming software:ISPSoft V2.04?196MB??Editing software for DVP series and AH500 series (Multilingual)
Note: please use with COMMGR for communication functionOperating System?Windows 2000, XP, Vista or Windows 7(32-bit/64-bit)
if necessary, to provide free
Introduction
1. Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP04DA-S series can read/write the data of analog output module by using instructions FROM/TO via DVP-PLC SS/SA/SX/SC/SV MPU program. The analog output module receives 12-bit digital data of 4 groups from PLC MPU and converts it into 4 points analog output signal either in voltage or in current.
2. The software version of DVP04DA-S analog output module can be updated via RS-485 communication. Power unit and module are separate. Size is small and easy to install.
3. Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10VDC (resolution is 2.5mV). Current output range is 0mA ~ 20mA (resolution is 5uA)
Specifications
Digital/Analog (2D/A) module
Voltage output
Current output
Power supply voltage
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog input channel
2 channels/each module
Analog output range
0 ~ 10V
0 ~ 20mA
Digital data range
0 ~ 4,000
0 ~ 4,000
Resolution
12 bits (1LSB=2.5mV)
12 bits (1LSB=5uA)
Output impedance
0.5? or lower
Overall accuracy
+-0.5% of full scale of 25°C (77°F).
+-1% of full scale during 0 ~ 55°C (32 ~ 131°F).
Response time
3ms × channels
Max. output current
20mA (1K? ~ 2M?)
--
Tolerance carried impedance
--
0 ~ 500?
Digital data format
2’s complementary of 16-bit, 13 significant bits.
Isolation method
Isolation between digital area and analog area. But no isolation among channels.
Protection
Voltage output has short circuit protection but a long period short circuit may cause internal wire damage and current output break.
Communication mode
(RS-485)
Yes, communication formats are (4,800/9,600/19,200/38,400/57,600/115,200
bps). Communication format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1). Communication format of RTU mode is 8 bits, even bit, 1 stop bit (8, E, 1).When connecting to PLC MPU in series, RS-485 can’t be used.
Connect to DVP-PLC MPU in series
If DVP04DA-S modules are connected to MPU, the modules are numbered from 0 - 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and they DO NOT occupy any digital I/O points of the MPU.
Max. rated power
consumption
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 4W, supply from external power.
Operation/storage
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2.
Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).
Vibration/shock immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)