Feature
The 1756 digital I/O modules support these features.
Variety of voltage interface capabilities
Isolated and nonisolated module types
Point-level output fault states
Direct-connect or rack-optimized communication
Field-side diagnostics on select modules
Specification
Outputs
16 electronically fused ((8 points/group)
Pilot duty
0.5 A
Voltage category
120/240V DC sink
Output delay time
Off to On
On to Off
9.3 ms @ 60 Hz
11 ms @ 50 Hz
9.3 ms @ 60 Hz
11 ms @ 50 Hz
Operating voltage range
74…265V AC
47…63 Hz
Current draw @ 5.1V
400mA
Current draw @ 24V
2 mA
Total backplane power
2.1 W
Power dissipation, max
6.5 W @ 60 °C (140 ?)
Thermal dissipation
22.17 BTU/hr
Off-state leakage current per point, max
3mA per point
On-state voltage drop, max
1.5V @ 0.5 A
5.7V @ load current < 50 mA
Current per point, max
0.5A @ 60 °C (140 ?)
Current per module, max
4A @ 60 °C (140 ?)
Surge current per point
15 A for 43 ms per Point, repeatable every 2 s @ 60°C (140 ?)
Load current, min
10 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current,
Littelfuse p/n H2153.15
Removable terminal block
1756-TBNH
1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1
North American temperature code
T4
Enclosure type
None (open-style)