No comment |
>
Control System >
PLC >
AB PLC >
1756-IR6I Allen-Bradley PLC 6 Channel Isolated RTD Input Module(20 Pin) New1756-IR6I Allen-Bradley PLC 6 Channel Isolated RTD Input Module(20 Pin) NewIf you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.PLCAGE:1756-IR6I Allen-Bradley PLC 6 Channel Isolated RTD Input Module(20 Pin) New
Feature
On-board data alarming
Scaling to engineering units
Real-time channel sampling
Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Module conversion method: Sigma-Delta
Module keying: Electronic software configurable
RTB keying: User-defined mechanical
Specification
Number of Inputs
6 individually isolated channels
Module Location
1756 ControlLogix Chassi
Backplane Power Requirements
(No external power requirements)
250mA @ 5.1V dc & 125mA @ 24V dc (4.25W)
Power Dissipation within Module
Thermal Dissipation
4.3W
14.66 BTU/hr
Input Range
1-487W, 2-1000W, 4-2000W, 8-4020W
Resolution in Ranges
487W
1000W
2000W
4020W
Approximately 16 bits across each input range
7.7mW/count
15mW/count
30mW/count
60mW/count
Sensors Supported
Resistance 4-4020W
100, 200, 500, 1000W Platinum, alpha=385
100, 200, 500, 1000W Platinum, alpha=3916
120W Nickel, alpha=672
100, 120, 200, 500W Nickel, alpha=618
10W Copper
Data Format
Integer mode (2s complement)
Floating point IEEE 32 bit
Open Circuit Detection Time
Positive full scale reading within 5s with any combination of lost
wires, except input terminal B alone.
If input terminal B is lost by itself, the module reads a negative
full scale reading within 5s.
Overvoltage Protection
24V ac/dc maximum
Normal Mode Noise Rejection
60dB at 60Hz
Common Mode Noise Rejection
120dB at 60Hz, 100db at 50Hz
Channel Bandwidth
15Hz
Settling Time to 5% of Full Scale
<80ms
Calibrated Accuracy at 25oC
Calibration Interval
Better than 0.1% of range
12 months typical
Input Offset Drift with Temperature
10mW/degree C
Gain Drift with Temperature
50 ppm/degree C typical (90 ppm maximum)
Module Error over Full Temp. Range
0.54% of range
Module Scan Time for all Channels
(Sample Rate)
25ms minimum floating point (ohms)
50ms minimum floating point (temperature)
10ms minimum integer (ohms)
Module Conversion Method
Sigma-Delta
Isolation Voltage
Channel to channel
User to system
Optoisolated, transformer isolated
100% tested at 1700V dc for 1s, based on 250V ac
100% tested at 1700V dc for 1s, based on 250V ac
Module Keying (Backplane)
Electronic
RTB Screw Torque (NEMA)
7-9 inch-pounds (0.8-1Nm)
RTB Keying
User defined mechanical keying
RTB and Housing
20 Position RTB (1756-TBNH or TBSH)
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
0 to 60°C (32 to 140°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
Screwdriver Width for RTB
5/16 inch (8mm) maximum
Cat. No.
Inputs/Outputs
Range
Resolution
Removable Terminal Block
1756-IR6I
6 individually isolated RTD inputs
1…487 W
2…1000 W
4…2000 W
8…4020 W16 bits
1…487 W: 7.7 mW/bit
2…1000 W: 15 mW/bit
4…2000 W: 30 mW/bit
8…4020 W: 60 mW/bit1756-TBNH
1756-TBSH1756-IT6I
6 individually isolated thermocouple inputs
1 CJC-12…78 mV
-12…30 mV16 bits
-12...78 mV: 1.4 mV/bit
-12...30 mV: 0.7 mV/bit1756-TBNH
1756-TBSH1756-IT6I2
6 individually isolated thermocouple inputs
2 CJC-12…78 mV (1.4 mV per bit)
-12…30 mV (0.7 mV per bit – high resolution range)16 bits
-12...78 mV: 1.4 Vm/bit
-12...30 mV: 0.7 mV/bit1756-TBNH
1756-TBSH
No comment |