Features
Separate communication modules are available for different networks. Install multiple communication modules into the ControlLogix backplane to bridge or route control and information data between different networks. You can route a message through a maximum of four chassis (eight communication hops). You do not need a ControlLogix controller in the chassis.
ControlLogix-XT communication modules for extreme environments are available for EtherNet/IP, ControlNet, and Data Highway Plus and Remote I/O networks.Specification
Attribute
1756-EN2F
1756-EN2T,
1756-EN2TSC
1756-EN2TR, 1756-EN3TR
1756-ENBT
1756-EWEBEtherNet/IP communication rate
100 Mbps
10/100 Mbps
10/100 Mbps
10/100 Mbps
Logix communication connections
256
TCP/IP communication connections
128
Current draw @ 5.1V DC
1.2 A
1 A
1 A
700 mA
Current draw @ 24V DC
3 mA
3 mA
3 mA
3 mA
Power dissipation
6.2 W
5.1 W
5.1 W
3.7 W
Thermal dissipation
21.28 BTU/hr
17.4 BTU/hr
17.4 BTU/hr
12.6 BTU/hr
Isolation voltage
No isolation between USB and
system
30V (continuous), basic
insulation type, Ethernet
network to backplane
No isolation between USB
and backplane
Type tested @ 510V AC for
60 s
30V (continuous), basic insulation
type, Ethernet network to backplane
No isolation between USB and
backplane
Type tested @ 853V AC for 60 s
30V (continuous), basic insulation
type, Ethernet network to backplane
Type tested @ 707V DC for 60 s
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
756-PA75R, 1756-PB75R, 1756-PSCA2
Ethernet port
1 Ethernet fiber
1 Ethernet RJ45 Category 5
1 Ethernet RJ45 Category 5
Ethernet cable
Multimode fiber, LC connector
802.3 compliant shielded or unshielded twisted pair
USB port
USB 1.1, full speed (12 Mbps)
-
Wiring category(
3 - on USB ports
3 - on USB ports
2 - on Ethernet ports
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)