Your Position: Home > Control System > PLC > AB PLC > 1746-NR8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Inputs 16 Bits New

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

1746-NR8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Inputs 16 Bits New

prevnext

1746-NR8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Inputs 16 Bits New
  • Market price: $ 3719.1
  • Shop price: $ 1127.0
  • Goods click count: 397
  • Total:
  • Quantity:
Add to cart collect
  

Description

1746-NR8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Inputs 16 Bits New

If you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.

PLCAGE: 1746-NR8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Inputs 16 Bits New

Features

The RTD module supplies a small current to each RTD connected to the module inputs (up to 8 input channels). The module provides on-board scaling and converts RTD input to temperature (°C °F or reports resistance input in ohms.)

Specification

 

1746-NR4

1746-NR8

Backplane Current Consumption

50 mA at 5V dc

50 mA at 24V dc

100 mA at 5V dc

55 mA at 24V dc

Backplane Power Consumption

1.5W maximum

(0.3 W at 5V dc, 1.2 W at 24V dc)

1.82W maximum

(0.5W at 5V dc, 1.32W at 24V dc)

External Power Supply Requirements

None

Number of Channels

4 (backplane isolated)

8 (backplane isolated)

I/O Chassis Location

Any I/O module slot except slot 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Low pass digital filter with programmable notch (filter) frequencies

Common Mode Rejection (between

inputs and chassis ground)

> 150 dB at 50 Hz (10 Hz and 50 Hz filter

frequencies)

> 150 dB at 60 Hz (10 Hz and 60 Hz filter

frequencies)

> 120 dB at 50 Hz (28 Hz and 50 Hz filter

frequencies)

> 120 dB at 60 Hz (28 Hz and 60 Hz filter

frequencies)

Normal Mode Rejection (between [+]

input and [-] input)

Greater than 100 dB at 50 Hz (10 Hz, 50 Hz filter

frequencies)

Greater than 100 dB at 60 Hz (10 Hz, 60 Hz filter

Frequencies)

65 dB at 50/60 Hz (with 50/60 Hz filter)

110 dB at 50 Hz (with 28 Hz filter)

95 dB at 60 Hz (with 28 Hz filter)

Maximum common mode voltage

± 1 volt

Maximum allowed permanent

overload

Volts: ± 5V dc

Current: ± 5mA

Input Filter Cut-Off Frequencies

2.62 Hz at 10 Hz filter frequency

13.1 Hz at 50 Hz filter frequency

15.72 Hz at 60 Hz filter frequency

65.5 Hz at 250 Hz filter frequency

7.80 Hz at 28 Hz filter frequency

13.65 Hz at 50/60 Hz filter frequency

209.6 Hz at 800 Hz filter frequency

1676 Hz at 6400 Hz filter frequency

Calibration

Module autocalibrates when power is applied, a

channel is enabled or when a change is made to

its input type, filter frequency, or excitation

current.

Set module calibration disable to zero to enable

module to autocalibrate when power is applied,

a channel is enabled, or when a change is made

to the input type, filter frequency, or excitation

current.

Isolation (optical)

500V dc continuous between inputs and chassis

ground, and between inputs and backplane

707V dc for 1 minute

Isolation Between Inputs

None

±5V dc

 








  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: