BMXP342000 processor module M340 - max 1024 discrete + 256 analog I/O – Modbus
Main
Commercial Status
Commercialised
Range of product
Modicon M340 automation platform
Product or component type
Processor module
Number of racks
1
Number of slots
11
Discrete I/O processor capacity
1024 I/O single-rack configuration
Analogue I/O processor capacity
66 I/O single-rack configuration
256 I/O multi-rack configurationNumber of application specific channel
36
Monitoring
Event counters Modbus
Diagnostic counters ModbusComplementary
Control channels
Programmable loops
Integrated connection type
USB port 12 Mbit/s
Non isolated serial link RJ45 Modbus master/slave RTU/ASCII asynchronous in baseband RS485 half duplex 0.3...19.2 kbit/s 1 twisted shielded pair
Non isolated serial link RJ45 Modbus master/slave RTU/ASCII asynchronous in baseband RS232C half duplex 0.3...19.2 kbit/s 1 twisted shielded pair
Non isolated serial link RJ45 character mode asynchronous in baseband RS485 half duplex 0.3...19.2 kbit/s 1 twisted shielded pair
Non isolated serial link RJ45 character mode asynchronous in baseband RS232C full duplex 0.3...19.2 kbit/s 2 twisted shielded pairsCommunication module processor
4 AS-Interface module
2 Ethernet communication moduleNumber of devices per segment
0...32 Modbus
0...32 character modeNumber of devices
2 point-to-point Modbus
2 point-to-point character modeBus length
0...15 m Modbus point-to-point
0...15 m character mode point-to-point
0...1000 m serial link isolated Modbus segment
0...1000 m serial link isolated character mode segment
0...10 m serial link non isolated Modbus segment
0...10 m serial link non isolated character mode segmentTap links length
0...40 m serial link isolated Modbus segment
0...40 m serial link isolated character mode segment
0...15 m serial link non isolated Modbus segment
0...15 m serial link non isolated character mode segmentNumber of addresses
0...248 Modbus
0...248 character modeRequests
504 data bytes per ASCII request Modbus
252 data bytes per RTU request Modbus
1 K data bytes per request character modeControl parameter
One LRC on each frame (ASCII) Modbus
One LRC on each frame (ASCII) character mode
One CRC on each frame (RTU) ModbusMemory description
Supplied memory card (BMXRMS008MP) for backup of programs, constants, symbols and data
1792 kB internal RAM for program constants and symbols
128 kB internal RAM for data
2048 kB internal RAMMaximum size of object areas
32760 %KWi constant words located internal data
32464 %MWi internal words located internal data
16250 %Mi located internal bits
128 kB unlocated internal dataDefault size of object areas
512 %MWi internal words located internal data
256 %Mi located internal bits
128 %KWi constant words located internal dataApplication structure
1 cyclic/periodic master task
1 periodic fast task
32 event tasks
No auxiliary taskExecution time per instruction
1.74 µs floating points
0.38 µs single-length words
0.26 µs double-length words
0.18 µs BooleanNumber of instructions per ms
5.4 Kinst/ms 100 % Boolean
4.2 Kinst/ms 65 % Boolean + 35 % fixed arithmeticSystem overhead
1.05 ms master task
0.2 ms fast taskCurrent consumption
72 mA 24 V DC
Supply
Internal power supply via rack
Marking
CE
Status LED
1 LED yellow activity on Modbus (SER COM)
1 LED red processor or system fault (ERR)
1 LED red memory card fault (CARD ERR)
1 LED red I/O module fault (I/O)
1 LED green processor running (RUN)Product weight
0.2 kg