No comment |
>
Control System >
Inverter >
3-Phase 400V 25A 11KW 15HP TECO Inverter N2-415-H3 NEW
Product Specifications
1/ 3 Phase 200-240 Volts
N2-xxx—xxx
2P5
201
202
203
205
208
210
215
220
230
Horse Power
1/2
1
2
3
5
7.5
10
15
20
30
Rated Motor KW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
22
Rated Current (A)
3.1
4.5
7.5
10.5
17.5
26
35
49
64
87
Output (KVA)
1.2
1.7
2.9
4.0
6.7
9.9
13.3
18.7
24.4
33.2
Input Voltage Max.
(1 / 3 Phase) (200~240 Volts +-10%) (50/60Hz +-5%) (5 h.p. & above 3 Phase Only)
Output Voltage Max.
3 Phase 200 ~ 240 (proportional to input voltage)
IP20 Weight (Kg)
1.4
1.4
2.5
4.0
4.0
6.8
7.1
12.3
12.5
13.8
Power Loss
Ride Through (s)
1
1
2
2
2
2
2
2
2
2
3 Phase 380 ~ 480 Volts
N2-xxx—xxx
401
402
403
405
408
410
415
420
430
Horse Power
1
2
3
5
7.5
10
15
20
30
Rated Motor KW
0.75
1.5
2.2
3.7
5.5
7.5
11
15
22
Rated Current (A)
2.3
3.8
5.2
8.8
13
17.5
25
32
48
Output (KVA)
1.7
2.9
4.0
6.7
9.9
13.3
19.1
24.4
36.6
Input Voltage Max
( 3 Phase 380 ~ 480 Volts +- 10%) (50/60Hz +- 5%)
Output Voltage Max.
3 Phase 380 ~ 480 Volts (proportional to input voltage)
IP20 Weight (Kg)
2.4
2.5
3.8
4.0
7.0
7.3
12.3
12.5
13.5
Power Loss
Ride Through (s)
1
1
2
2
2
2
2
2
2
Functional Specification
Control
Characteristics
Carrier frequency
1 - 12 K
Frequency Control Range
0.1 – 400 Hz
Frequency Accuracy
Digital: 0.01% (-10 ~ 40 °C); Analog: 0.4% (25+-10 °C)
Frequency Resolution
0.01 Hz with computer or PLC control, 0.1 Hz with keypad control when freq.
above 100 Hz
Frequency Setting Signal
(0-5VDC) (0-10VDC) (4-20mA) (0-20mA)
Accel / Decel Time
0.1-3600 SEC with (2) S-curves
Braking Torque
About 20% (built-in Braking transistor)
V/F Pattern
18 patterns, one curve programmable
Protection Function
Instantaneous Over Current
Approx. 200% rated current
Overload
T-verter: 150% / 1 minute
Motor Overload Protection
Electronic thermal overload relay
Over voltage
200V series: (DC bus voltage exceeds 427V)
400v series: (DC bus voltage exceeds 854V)
Under voltage
200V series: (DC bus voltage drops < 200V)
400v series: (DC bus voltage drops < 400V)
Momentary Power Loss
0~2 seconds: The T-verter can be restarted using the speed search feature
Heat Sink Fin Overheat
Protected by thermister
Ground Fault
Electronic circuit protection
Operation Conditions
Input Signal
Operation signals
Forward/Reverse operation, by keypad or hardwire contact, multiple individual commands
Reset
Released protection while the protective function is operating
Multifunction Input
Refer to function illustration in Fn_56
Output Signal
Multifunction Output
Refer to function illustration in Fn_61
Fault output
250VAC 1A, 30VDC 1A or less
Built-in Function
Frequency reference bias/gain; up/lower limit; manual torque boost; frequency meter calibrating gain; auto restart attempt; skip frequency; S-curve ACCEL/DECEL; Carrier frequency adjust.(1-12KHz)
Communication link function
Digital operator monitor
Frequency command, output frequency, speed, output current, output voltage, P-N bus voltage, rotating direction
Analog Output Monitor
Analog output (0-10V), possible to select output frequency & setting freq. & output voltage & P-N bus voltage
Environmental
Location
Indoor (protected from corrosive gas and dust)
Ambient Temperature
-10 degrees ~ 40 degrees © 50 degrees with cover removed
Humidity
0-95%(non condensing)
Vibration
0.5G
Enclosure
IP20 / IP65 (NEMA4)
EMC
EN50081-1, EN50082-2 (with optional filter)
LVD
EN50178
UL
UL 508C
N2-205 and above capacity are not CE complied
Wiring
No comment |