No comment |
>
Control System >
PLC >
Schneider PLC >
TWDLCAA24DRF Twido PLC CPU Supply Voltage 100~240VAC 14DI 10DO RelayTWDLCAA24DRF Twido PLC CPU Supply Voltage 100~240TWDLCAA24DRF Twido PLC CPU Supply Voltage 100~240VAC 14DI 10DO Relay |
TWDLCAA24DRF
TWDLCAA24DRF extendable PLC base Twido – 100-240 V AC supply - 14 I 24 V DC - 10 O relay
Main
Range of product | Twido |
Product or component type | Compact base controller |
Discrete I/O number | 24 |
Discrete input number | 14 |
Discrete input voltage | 24 V |
Discrete input voltage type | DC |
Discrete output number | 10 relay |
Number of I/O expansion module | 4 |
[Us] rated supply voltage | 100...240 V AC |
Use of slot | Memory cartridge or realtime clock cartridge |
Data backed up | Internal RAM (lithium) 30 days , 10 hrs , 10 yr |
Integrated connection type | Non isolated serial link mini DIN, Modbus/character mode master/slave RTU/ASCII (RS485) half duplex , 38,4 kbit/s |
Complementary function | PID |
Complementary
Discrete input logic | Sink or source |
Input voltage limits | 20.4...28.8 V |
Discrete input current | 7 mA I0.2 to I0.13 |
Input impedance | 2100 Ohm I0.0 to I0.1 |
Filter time | 35 µs + programmed filter time for I0.0 to I0.5 at state 1 |
Insulation between channel and internal logic | 1500 Vrms for 1 minute |
Insulation resistance between channel | None |
Minimum load | 0,1 mA |
Contact resistance | ≤ 30000 µOhm |
Load current | 2 A 240 V AC resistive 30 cyc/mn relay outputs |
Mechanical durability | ≥ 20000000 cycles relay outputs |
Electrical durability | ≥ 100000 cycles relay outputs |
Current consumption | 5 mA 5 V DC at state 0 |
I/O connection | Non-removable screw terminal block |
Input/output number | ≤ 120 spring terminal block with I/O expansion module |
Network frequency | 50/60 Hz |
Supply voltage limits | 85...264 V |
Network frequency limits | 47...63 Hz |
Power supply output current | 0,25 A 24 V DC sensors |
Power supply input current | 450 mA |
Inrush current | ≤ 40 A |
Protection type | Power protection internal fuse |
Power consumption in VA | 33 VA 100 V |
Insulation resistance | > 10 MOhm at 500 V, between supply and earth terminals |
Program memory | 3000 instructions |
Exact time for 1 K instruction | 1 ms |
System overhead | 0,5 ms |
Memory description | Internal RAM , 256 internal bits, no floating, no trigonometrical |
Free slots | 1 |
Realtime clock | Without |
Counting input number | 1 channel 20000 Hz 32 bits |
Analogue adjustment points | 1 point adjustable from 0...1023 |
Marking | CE |
Status LED | 1 LED green PWR |
Product weight | 0,305 kg |
TWDLCAA24DRF Twido PLC CPU Supply Voltage 100~240VAC 14DI 10DO Relay
TWDLCAA24DRF
TWDLCAA24DRF extendable PLC base Twido – 100-240 V AC supply - 14 I 24 V DC - 10 O relay
Main
Range of product
Twido
Product or component type
Compact base controller
Discrete I/O number
24
Discrete input number
14
Discrete input voltage
24 V
Discrete input voltage type
DC
Discrete output number
10 relay
Number of I/O expansion module
4
[Us] rated supply voltage
100...240 V AC
Use of slot
Memory cartridge or realtime clock cartridge
Data backed up
Internal RAM (lithium) 30 days , 10 hrs , 10 yr
Integrated connection type
Non isolated serial link mini DIN, Modbus/character mode master/slave RTU/ASCII (RS485) half duplex , 38,4 kbit/s
Power supply
Serial link interface adaptor (RS232C/RS485)Complementary function
PID
Event processingComplementary
Discrete input logic
Sink or source
Input voltage limits
20.4...28.8 V
Discrete input current
7 mA I0.2 to I0.13
11 mA I0.0 to I0.1Input impedance
2100 Ohm I0.0 to I0.1
3400 Ohm I0.2 to I0.13Filter time
35 µs + programmed filter time for I0.0 to I0.5 at state 1
40 µs + programmed filter time for I0.6 to I0.13 at state 1
45 µs + programmed filter time for I0.0 to I0.5 at state 0
150 µs + programmed filter time for I0.6 to I0.13 at state 0Insulation between channel and internal logic
1500 Vrms for 1 minute
Insulation resistance between channel
None
Minimum load
0,1 mA
Contact resistance
≤ 30000 µOhm
Load current
2 A 240 V AC resistive 30 cyc/mn relay outputs
2 A 30 V DC resistive 30 cyc/mn relay outputs
2 A 240 V AC inductive 30 cyc/mn relay outputs
2 A 30 V DC inductive 30 cyc/mn relay outputsMechanical durability
≥ 20000000 cycles relay outputs
Electrical durability
≥ 100000 cycles relay outputs
Current consumption
5 mA 5 V DC at state 0
36 mA 5 V DC at state 1
55 mA 24 V DC at state 1I/O connection
Non-removable screw terminal block
Input/output number
≤ 120 spring terminal block with I/O expansion module
≤ 152 HE-10 connector with I/O expansion module
≤ 88 removable screw terminal block with I/O expansion moduleNetwork frequency
50/60 Hz
Supply voltage limits
85...264 V
Network frequency limits
47...63 Hz
Power supply output current
0,25 A 24 V DC sensors
Power supply input current
450 mA
Inrush current
≤ 40 A
Protection type
Power protection internal fuse
Power consumption in VA
33 VA 100 V
40 VA 264 VInsulation resistance
> 10 MOhm at 500 V, between supply and earth terminals
> 10 MOhm at 500 V, between I/O and earth terminalsProgram memory
3000 instructions
Exact time for 1 K instruction
1 ms
System overhead
0,5 ms
Memory description
Internal RAM , 256 internal bits, no floating, no trigonometrical
Internal RAM , 3000 internal words, no floating, no trigonometrical
Internal RAM , 128 timers, no floating, no trigonometrical
Internal RAM , 128 counters, no floating, no trigonometrical
Internal RAM , double words, no floating, no trigonometricalFree slots
1
Realtime clock
Without
Counting input number
1 channel 20000 Hz 32 bits
3 channels5000 Hz 16 bitsAnalogue adjustment points
1 point adjustable from 0...1023
1 point adjustable from 0 to 511 pointsMarking
CE
Status LED
1 LED green PWR
1 LED green RUN
1 LED red module error (ERR)
1 LED user pilot light (STAT)
1 LED per channel green I/O statusProduct weight
0,305 kg
No comment |