We will quote you our best price to you in 24hours.Specifications:
Model
CPU306EX
K306EX-24AT
K306EX-24AR
Technical Specification
CPU
16-Bit Industrial
Execution Speed
Typical Bool Instruction Time: <0.5 μS
Word Operation Time: <48μS
Arithmetic Operation Time for Integers: <65μS
Arithmetic Operation Time for Floating Points: <150μS
DI Points
14XDC24V
DO Points
10XDC24V
10Xrelay
User Program Memory
FRAM, 32KB/About 4,000 Steps
Program Backup
Permanent Storage, Without the Need of Battery
Memory Area
Variable Storage Area (V Area): 4KB
System Storage Area (SM Area): 300 Bytes
Internal Storage Area (M Area): 32 Bytes
Data Retention Characteristic
Configure with the Programming Software: V Area, C (Counter) Area
Retention Mode and Period
Adopt Super Capacitors and Support a Retention Period of Not Less than 144 Hours Upon Power Failure Under Normal Temperature.
Data Backup Characteristic
Perform Backup Operations VB3648~VB3902 According to User Instructions, 255 Bytes in Total
Backup Mode and Time
FRAM, 255 Bytes in Total (Writing Operation for 10 Billion Times), Permanent Backup
Floating Points
Supported; the whole V area can be used for floating points
Programming Language Supported
Ladder Drawing (LD), Instruction List (IL)
Instruction Set
Basic instructions: 114; expansion instructions: 420
Password Protection
Yes
Max. I/O
Digital data: 280 in total (256 DI and 256 DO respectively);
Analog data: 60 in total (32AI and 32 AO respectively)
Counter
256
Operation Mode of Counter
Addition, subtraction
Counter Range
-32768~32767
Counting Value Retention Function
Yes
Timer
256
1 ms Time Base: 4
10 ms Time Base: 16
100 ms Time Base: 236
High-speed Counter
6 High-Speed Counters
Where, Single-Phase Counters: 6, With a Maximum Frequency of 30 KHz
Where, Dual-Phase Counters: 4, with a Maximum Frequency of 20 KHz
Pulse Output
2, PTO (Pulse Train Output)/PWM (Pulse Width Modulation Output);
Maximum Output Frequency: 20 KHz(Note: the relay output CPU does not have high speed pluse function)
Analog Potentiometer
2, 10-bit Resolution, Values Corresponding to Internal Registers
Interruption Function
Timing Interruption: 2, 1ms Resolution;
Timer Interruption: T2/T3, 1ms Resolution;
Edge Interruption: 4, Rising Edge or Falling Edge Optional;
High-Speed Interruption, Communication Interruption
Real-time Clock
Yes, With an Error Not Greater than 2 Minutes/Month Under a Temperature of 25°C
The user can use the Software to Set/Read: Year, Month, Day, Hour, Minute, Second, Week. Adopt Super Capacitors and Support a Retention Period of Not Less than 144 Hours Upon Power Failure Under Normal Temperature.
Number of Connectable Expansion Modules
15; Regardless of Types
COM Port
2, RS232 or RS485;
Supported Working Modes: Programming,
Modbus-RTU (Master/Slave), Free Protocol
Equipment Connected with COM Port
RS232/RS485: PC (for programming), third-party HMI panel, Third-Party Serial Communication Equipment (For Example, Instruments, Bar Code Reader, etc.)
Input Power Supply
AC85~265V
Sensor Load Power Supply
DC24V, Max. 500 mA
Dimensions (L*W*H)
125X114X70mm