DVP06AD-S Delta PLC 6 point 14-bit resolution Analog I/O Module Original brand newDVP06AD-S Delta PLC 6 point 14-bit resolution Analog I/O Module Original brand new
Introduction
1. Thank you for choosing Delta DVP series. The analog signal input module DVP06AD-S is able to receive 6 points of external analog signal inputs (both in voltage and current) and convert the signals into 14-bit digital ones. It is able to read and write the data in the module through FROM/TO instructions given by the program of DVP-PLC SS/SA/SX/SC/SV series MPU. There are 49 16-bit control registers in the module.
2. The user can select voltage or current output by wiring. Range of voltage output: +-10V DC (resolution: 1.25mV). Range of current output: +-20mA (resolution: 5uA).
Specifications
Analog/Digital
(6A/D) module
Voltage input
Current input
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
6 channels/module
Range of analog input
+-10V
+-20mA
Range of digital
conversion
+-8,000
+-4,000
Resolution
14 bits (1LSB=1.25mV)
13 bits (1LSB=5uA)
Input impedance
200K? or more
250?
Overall accuracy
+-0.5% when in full scale (25°C, 77°F)
+-1% when in full scale in the range of 0 ~ 55°C, 32 ~ 131°F
Response time
3ms × the number of channels
Isolation
Isolation between digital area and analog area. No isolation among channels.
Range of absolute input
+-15V
+-32mA
Digital data format
13 significant bits out of 16 bits are available; in 2’s complement.
Average function
Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20.
Self-diagnosis
Upper and lower bound detection/channel
Communication mode
(RS-485)
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU in series.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU.
Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/Opoints.
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied by external power.
Operation/storage
Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2.
Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27 (TEST Ea)
Product Profile & Outline