PLC 4 AI 2 AO Module Delta DVP06XA-S Delta New
PLC 4 AI 2 AO Module Delta DVP06XA-S Delta New
Description
1. DVP06XA-S is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-S receives 2 groups of
12-bit digital data from the PLC MPU and converts them into 2 points of analog signals for output (in voltage/current). There are 49 16-bit control registers (CR) in DVP06XA-S, and the data in it can be read and written by using FROM/TO instructions in DVP Slim series PLC MPU program.
2. The system version of DVP06XA-S can be updated via RS-485 communication. The power unit is separate from it and is small in size and easy to install.
3. The user can select voltage or current input by wiring. Range of voltage input: +-10VDC (resolution: 5mV). Range of current input: +-20mA (resolution: 20uA).
4. The user can also select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5uA).
Specifications
Mixed analog/digital (A/D)
module
Voltage input
Current input
Power supply voltage
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog input channel
4 channels per module
Analog input range
+-10V
+-20mA
Digital data range
+-2,000
+-1,000
Resolution
12 bits (1LSB=5mV)
11 bits (1LSB=20uA)
Input impedance
200K? and above
250?
Overall accuracy
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F).
Response time
3ms × channels
Isolation method
There is no isolation between channels
Absolution input range
+-15V
+-32mA
Digital data format
2’s complement of 16-bit, (13 significant bits)
Average function
Yes (CR#2 ~ CR#5 can be set and the range is K1 ~ K4,095)
Self diagnostic function self detection
Upper bound and lower bound detection per channel
Mixed digital/analog (D/A)
module
Voltage output
Current output
Analog signal output channels
2 channel per module
Analog output range
0 ~ 10V
0 ~ 20mA
Digital data range
0 ~ 4,000
0 ~ 4,000
Resolution
12 bits (1LSB=2.5mV)
12 bits (1LSB=5uA)
Output impedance
0.5? or lower
Overall accuracy
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F)
Response time
3ms × channels
Max. output current
20mA (1K? ~ 2M?)
/
Tolerance carried impedance
/
0 ~ 500?
Digital data format
2’s complement of 16-bit, (13 significant bits).
Isolation method
Isolation between digital and analog circuitry. There is no isolation between channels.
Protection
Voltage output has short circuit protection but long period of short circuit may cause internal wiring damage and current output break.
Communication mode
(RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP06XA-S is connected in series with MPU.
Connect to DVP-PLC MPU
in series
When DVP06XA-S modules are connected to an MPU, the modules are numbered from 0-7. 0 is the closest to the MPU and 7 is the furthest. The Maximum number of modules is 8 modules and they do not occupy any digital I/O points of the MPU.
Power supply
Maximum power consumption
2W at 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), supplied by external power
Environment
Operation/storage
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2.
Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).
Vibration/shock immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)