No comment |
>
Transducer/Sensor >
Photoelectric Sensors >
Photoelectric Switch >
TL-N20MD1 Proximity Switch NEWTL-N20MD1 OMRON Proximity Switch NEWOMRON Proximity Switch TL-N20MD1
Product Description:
Easy installation, high-speed pulse generator, high-speed rotation control, and more.
Direct mounted to metal (-N Models).
A wealth of models ideal for limit control, counting control, and other applications (-N Models).
Specifications:
Model
TL-Q5MD[]
TL-N7MD[]
TL-N12MD[]
TL-N20MD[]
Sensing distance
5 mm ±10%
7 mm ±10%
12 mm ±10%
20 mm ±10%
Set distance
0 to 4 mm
0 to 5.6 mm
0 to 9.6 mm
0 to 16 mm
Differential travel
10% max. of sensing distance
Detectable object
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on Data Sheet.)
Standard sensing object
Iron, 18 × 18 × 1 mm
Iron, 30 × 30 × 1 mm
Iron, 40 × 40 × 1 mm
Iron, 50 × 50 × 1 mm
Response frequency *
500 Hz
300 Hz
Power supply voltage
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
(operating voltage range)
Leakage current
0.8 mA max.
Control
Load current
3 to 100 mA
output
Residual
3.3 V max. (Load current: 100 mA, Cable length: 2 m)
voltage
Indicators
D1 Models: Operation indicator (red), Setting indicator (green)
D2 Models: Operation indicator (red)
Operation mode (with
D1 Models: NO, D2 Models: NC
sensing object approaching)
Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.
Protection circuits
Load short-circuit protection, Surge suppressor
Ambient temperature range
Operating/Storage: -25 to 70°C (with no icing or condensation)
Ambient humidity range
Operating/Storage: 35% to 95% (with no condensation)
Temperature influence
±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C
Voltage influence
±2.5% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance
50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength
1,000 VAC for 1 min between current-carrying parts and case
Vibration resistance
Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
Destruction: 500 m/s2
Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions
3 times each in X, Y,
and Z directions
Degree of protection
IEC 60529 IP67, in-house standards: oil-resistant
Connection method
Pre-wired Models (Standard cable length: 2 m)
Weight (packed state)
Approx. 45 g
Approx. 145 g
Approx. 170 g
Approx. 240 g
Materials
Case
Heat-resistant ABS
Sensing
surface
Accessories
Instruction manual
Mounting Bracket,
Mounting Bracket,
Mounting Bracket,
Mounting phillips screws
Mounting phillips screws
Mounting phillips screws
(M4 × 25),
(M4 × 30),
(M5 × 40),
Instruction manual
Instruction manual
Instruction manual
*The response frequency is an average value.
Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance.
No comment |