No comment |
>
Transducer/Sensor >
Photoelectric Sensors >
Photoelectric Switch >
E2EM-X30MX1 Proximity Switch NEWE2EM-X30MX1 OMRON Proximity Switch NEWProduct Description:
Long-distance detection at up to 30 mm enables secure mounting with reduced problems due to workpiece collisions.
No polarity for easy wiring with DC 2-wire models.
Cable protector provided as a standard feature.
Specifications:
Size
M12
M18
M30
Shielded
Shielded
Shielded
Unshielded
Shielded
Unshielded
Model
E2EM-X4X[]
E2EM-X8X[]
E2EM-X16MX[]
E2EM-X15X[]
E2EM-X30MX[]
Sensing distance
4 mm ±10%
8 mm ±10%
16 mm ±10%
15 mm ±10%
30 mm ±10%
Set distance *1
0 to 3.2 mm
0 to 6.4 mm
0 to 12.8 mm
0 to 12 mm
0 to 24 mm
Differential travel
15% max. of sensing distance
Detectable object
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Datasheet.)
Standard sensing object
Iron, 12 × 12 × 1 mm
Iron, 18 × 18 × 1 mm
Iron, 45 × 45 × 1 mm
Iron, 30 × 30 × 1 mm
Iron, 70 × 70 × 1 mm
Response frequency *2
1 kHz
0.5 kHz
0.4 kHz
0.25 kHz
0.1 kHz
Power supply voltage
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
(operating voltage range)
Leakage current
0.8 mA max.
Control
Load
3 to 100 mA
output
current
Residual
5 V max. (Load current: 100 mA, Cable length: 2 m)
voltage *3
Indicators
X1 Models: Operation indicator (red), Setting indicator (green)
X2 Models: Operation indicator (red)
Operation mode
X1 Models: NO
(with sensing object
X2 Models: NC
approaching)
Refer to Datasheet.
Protection circuits
Surge suppressor, Load short-circuit protection
Ambient temperature range
Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation)
Ambient humidity range
Operating/Storage: 35% to 95% (with no condensation)
Temperature influence
±15% max. of sensing distance at 23°C in the temperature range of -25 to 70°C
Voltage influence
±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance
50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength
1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case
Vibration resistance
Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions
Degree of protection
IEC 60529 IP67, in-house standards: oil-resistant
Connection method
Pre-wired Models (Standard cable length: 2 m)
Weight (packed state)
Approx. 60 g
Approx. 130 g
Approx. 150 g
Approx. 180 g
Approx. 210 g
Materials
Case
Nickel-plated brass
Sensing
PBT
surface
Clamping
Nickel-plated brass
nuts
Toothed
Zinc-plated iron
washer
Accessories
Instruction manual
*1.Use the Sensor within the range in which the setting indicator (green LED) is ON (except X2 Models).
*2.The response frequency is an average value.
Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance.
*3.The residual voltage is 5 V. Make sure that the device connected to the Sensor can withstand the residual voltage. (Refer to Datasheet.)