No comment |
>
Transducer/Sensor >
Photoelectric Sensors >
Photoelectric Switch >
E2E-X2D1-N Standard Proximity Sensor NEWE2E-X2D1-N Omron Standard Proximity Sensor NEWProduct Description:
DC 2-Wire Model , Unshielded , M30 , Sensing Distance 20mm , Operation Mode NO ,.
Specifications:
Cylinder type sensing head size
M30
Type
Unshielded
Sensing method
Inductive type
Sensing distance
20 mm -10% to +10%
Setting distance
0 to 16 mm
Differential distance
10% Max. of sensing distance
Sensing object
Ferrous metal (Sensitivity lowers with non-ferrous metals.)
Standard sensing object
Iron 54*54*1mm
Response frequency
DC: 0.1 kHz (average)
Power supply voltage
12 to 24 VDC (ripple(p-p) :10% Max.)
Operating voltage range
10 to 30 VDC
Leakage current
0.8 mA Max.
Control output (Output type)
DC 2-wire models with polarity
Control output (Switching capacity)
3 to 100 mA
Control output (Residual voltage)
(DC) 3 V Max. ?under load current with cable length of 2m?
Indicator
Operation indicator(red), Operation setting indicator(green)
Operation mode
NO
Protective circuit
Surge suppressor
Output short-cut protection
Standard or Different frequency
Standard
Ambient temperature
Operating: -25 to 70 CEL
Storage: -40 to 85 CEL
(with no icing or condensation)
Ambient humidity
Operating: 35 to 95 %RH
Storage: 35 to 95 %RH
(with no condensation)
Temperature influence
+-10% Max. of sensing distance in temperature range of -25 to +70CEL
(As the basis for sensing distance of 23CEL)
Voltage influence
+-1% Max. of sensing distance in rated voltage range +-15%. (As the basis for sensing distance at standard power voltage)
Insulation resistance
50 M OHM Min. at 500VDC between charged parts and the case
Dielectric strength
1000 VAC 50/60 Hz for 1 minute between charged parts and the case
Vibration resistance
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
1000m/s2 for 10 times each in X, Y, and Z directions
Degree of protection
IEC60529: IP67
Applicable standard (EC Directive (Low Voltage Directive))
EN60947-1
EN60947-5-2
Applicable standard (EC Directive (EMC Directive))
EMI: EN60947-5-2
Emission Enclosure: CISPR11 Group 1 class A
EMS: EN60947-5-2
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Burst: IEC61000-4-4
CE marking: Equipped
Applicable standard (CCC mark)
Not equipped
Connection method
M12 connector models
Weight (Packed state)
approx. 90 g
Material (case)
Brass nickel plating
Material (sensing surface)
PBT
Material (clamping nuts)
Brass nickel plating
Material (toothed washer)
Iron zinc plating
Accessories
Instruction manual
No comment |