No comment |
>
Transducer/Sensor >
Photoelectric Sensors >
Photoelectric Switch >
E2A-M18KS08-M1-C2 E2A Cylindrical Proximity Sensor NEWE2A-M18KS08-M1-C2 Omron E2A Cylindrical Proximity Sensor NEWProduct Description:
Safe Mounting with Greater Sensing Distance
• Ensures a sensing distance approximately 1.5 to 2m times larger than that of any conventional OMRON Sensor.
• Problems such as the collision of workpieces are eliminated.
• Full range of standard sizes (M8, M12, M18 and M30; both long and short barrels)
• Modular construction simplifies customization.
Specifications:
Size
M18
M30
Type
Shielded
Non-shielded
Shielded
Non-shielded
Non-shielded
Item
E2A-M18?S08-??-B?
E2A-M18?S08-??-C?E2A-M18?N16-??-B?
E2A-M18?N16-??-C?E2A-M30?S15-??-B?
E2A-M30?S15-??-C?E2A-M30KN20-??-B?
E2A-M30KN20-??-C?E2A-M30LN30-??-B?
E2A-M30LN30-??-C?Sensing distance
8 mm±10%
16 mm±10%
15 mm±10%
20 mm±10%
30 mm±10%
Setting distance
0 to 6.4 mm
0 to 12.8 mm
0 to 12 mm
0 to 16 mm
0 to 24 mm
Differential travel
10% max. of sensing distance
Target
Ferrous metal (The sensing distance decreases with non-ferrous metal.)
Standard target (mild steel ST37)
24×24×1 mm
48×48×1 mm
45×45×1 mm
60×60×1 mm
90×90×1 mm
Response frequency (See note 1.)
500 Hz
400 Hz
250 Hz
100 Hz
100 Hz
Power supply voltage (operating voltage range)
12 to 24 VDC. Ripple (p-p): 10% max. (10 to 32 VDC)
Current consumption (DC 3-wire)
10 mA max.
Output type
-B models: PNP open collector -C models: NPN open collector
Load current (See note 2.)
Load current (See note 2.)
Residual voltage
2 V max. (under load current of 200 mA with cable length of 2 m)
Indicator
Operation indicator (Yellow LED)
Operation mode (with sensing object approaching)
-B1/-C1 models: NO -B2/-C2 models: NC For details, refer to the timing charts.
Protection circuit
Output reverse polarity protection, Power source circuit reverse polarity protection, Surge suppressor, Short-circuit protection
Ambient air temperature
Operating: −40°C to 70°C, Storage: −40°C to 85°C (with no icing or condensation)
Temperature influence (See note 2.)
±10% max. of sensing distance at 23°C within temperature range of −25°C to 70°C ±15% max. of sensing distance at 23°C within temperature range of −40°C to 70°C
Ambient humidity
Operating: 35% to 95%, Storage: 35% to 95%
Voltage influence
±1% max. of sensing distance in rated voltage range ±15%
Insulation resistance
50 MΩ min. (at 500 VDC) between current carry parts and case
Dielectric strength
1,000 VAC at 50/60 Hz for 1 min between current carry parts and case
Vibration resistance
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y and Z directions
Shock resistance
1,000 m/s2, 10 times each in X, Y and Z directions
Standard and listings
IEC60529: IP67, Degree of protection EN60947-5-2: EMC UL (CSA) [E196555] (See note 3.)
Connection method
-WP models: Pre-wired models (Standard length: 2 m) -M1 models: M12 4-pin connector models -M5 models: M8 3-pin connector models
Weight (packaged) Pre-wired model
Approx. 160 g
Approx. 280 g
Approx. 280 g
Approx. 370 g
Weight M12 connector model
Approx. 70 g
Approx. 200 g
Approx. 200 g
Approx. 260 g
Case
Brass-nickel plated
Sensing surface
PBT
Cable
PVC
Clamping nut
Brass-nickel plated
Note:
1. The response frequency is an average value. Measurement conditions are as follows: standard target, a distance of twice the standard target distance between targets, and a setting distance of half the sensing distance.
2. When using any model at an ambient temperature between −40°C and −25°C and a power voltage between 30 and 32 VDC, use a load current of 100 mA max.,
3. UL (CSA) [E196555]: Use class 2 circuit only.
No comment |