Climatic Environmental Conditions
Temperature
Operating
-horizontal design
0 to+60° C (32 to 140° F)
-vertical design
0 to+40° C (32 to 104° F)
(Air-intake temperature, measured on the underside of the module)
Nonoperating
- 40 to +70° C
(- 40 to +150° F)
Temperature change
-operating
max. 10° C/h (50° F/h)
-non operating
max. 20° C/h (68° F/h)
Relative humidity
to DIN 40040 15 to 95% (indoors), noncondensing
Atmospheric pressure
-operating
860 to 1060 hPa
-non operating
660 to 1060 hPa
Pollutants
-SO2
0.5 ppm,
(rel. humidity 60%, noncondensing)
-H2S
0.1 ppm,
(rel. humidity 60%, noncondensing)
Mechanical Environmental Conditions
Vibration*
-tested to IEC 68-2-6
10 to 57 Hz,
Const. ampl. 0.075 mm
57 to 150 Hz,
Const. accel. 1 g
Mode of vibration
Frequency sweeps with a sweep rate of 1 octave/min
Vibration period
10 frequency sweeps per axis in each of the 3 axes vertical to each other
Shock*
-tested to IEC 68-2-27
Type of shock
Half sine
Strength of shock
15 g peak value, 11 ms duration
Direction of shock
2 shocks in each of the 3 axes vertical to each other
Free-fall
to IEC 68-2-31
-tested with
height of fall 50 mm
Electromagnetic Compatibility (EMC) Noise Immunity
Static electricity
to IEC 801-2
(discharge on all parts that are accessible to the operator during normal operation)
-Test voltage
2.5 kV
(relative humidity 30 to 95%)
Radiated electromagnetic
to IEC 801-3
field test
field strength 3 V/m
Fast transient burst
to IEC 801-4, class III
Power supply
modules
-Supply voltage 24 V DC
1 kV
-Supply voltage 115/230 V AC
2 kV
-Analog input/output modules
1 kV
-Digital input/output modules
for V = 24 V
1 kV
for V > 24 V
2 kV
Communications
interface
1 kV
Emitted interference
to VDE 0871 Limit value class A
IEC/VDE Safety Information
Degree of protection
to IEC 529
-Type
IP 20
-Class
to IEC 536
Insulation rating
to VDE 0160
-between electrically
(05. 1988)
independent circuits
and
with circuits connected to a central grounding
point
to VDE 0160
-between all circuits
(05. 1988)
and
a central grounding point
(standard mounting rail)
to VDE 0160 (05. 1988)
Test voltage
Sine, 50 Hz
for a rated voltage
Vinput of the circuits (AC/DC)
Vinput = 0 to 50 V
500 V
Vinput = 50 to 125 V
1250 V
Vinput = 125 to 250 V
1500 V