No comment |
>
Control System >
PLC >
Siemens PLC >
6ES7450-1AP00-0AE0 SIEMENS Counter Module New6ES7450-1AP00-0AE0 SIEMENS Counter Module NewSIEMENS Counter Module 6ES7450-1AP00-0AE0
Product Description:
SIMATIC S7-400, FM 450-1 FUNCTION MODULE F. COUNT.FUNCT. WITH 2 CHANNELS INCL. CONFIG. PACKAGE ON CD.
Features:
Supply voltage
Load voltage 1L+
Reverse polarity protection
Yes
Load voltage 2L+
Reverse polarity protection
Yes
Aux. voltage 1L+, load voltage 2 L+
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V; Dynamic 18.5 V
permissible range, upper limit (DC)
28.8 V; dynamic 30.2 V
non-periodic skip
Duration
500 ms
Recovery time
50 s
Value
35 V
Input current
from load voltage 1L+ (without load), max.
40 mA
from backplane bus 5 V DC, max.
450 mA
Encoder supply
5 V encoder supply
5 V
Yes; 5.2 V +/-2%
Short-circuit protection
Yes
Output current, max.
300 mA
24 V encoder supply
24 V
Yes; 1L+ (-3 V)
Short-circuit protection
Yes
Output current, max.
300 mA
Power losses
Power loss, typ.
9 W
Digital inputs
Number/binary inputs
6
Functions
1 for gate start, 1 for gate stop, 1 for setting the counter
Input voltage
for signal "0"
-28.8 to +5 V
for signal "1"
+11 to +28.8 V
Input current
for signal "1", typ.
9 mA
Input delay (for rated value of input voltage)
Input frequency (with a time delay of 0.1 ms), max.
200 kHz
for standard inputs
Parameterizable
Yes
at "0" to "1", max.
2.5 µs; >= 2.5 µs (200 kHz); <= 25 µs (20 kHz)
Digital outputs
Number/binary outputs
6
Functionality/short-circuit strength
Yes; Clocked electronically
Limitation of inductive shutdown voltage to
2L+ (-39 V)
Output voltage
for signal "0", max.
3 V
for signal "1", min.
2L+ (-1.5 V)
Output current
for signal "1" rated value
0.5 A
for signal "1" permissible range for 0 to 60 °C, min.
5 mA
for signal "1" permissible range for 0 to 60 °C, max.
0.6 A
Output delay with resistive load
0 to
300 µs
Encoder
Connectable encoders
Incremental encoder (symmetrical)
Yes; With 2 pulse trains offset by 90°
Incremental encoder (asymmetrical)
Yes
24 V initiator
Yes
24 V directional element
Yes; 1 pulse train, 1 direction level
Interrupts/diagnostics/status information
Status indicator
Yes; 14 green LEDs for status of CR, DIR, inputs and outputs
Alarms
Diagnostic alarm
Yes; Parameterizable
Hardware interrupt
Yes; Parameterizable
Diagnostic messages
Diagnostic functions
Yes
Diagnostics
Yes; Diagnostic information readable
Diagnostics indication LED
Description
2 red LEDs for internal and external errors
Status indicator digital output (green)
Yes
Status indicator digital input (green)
Yes
Counter
Number of counter inputs
2; 32 bit or +/-31 bit
Counter input 5 V
Type
RS 422
Terminating resistor
220 Ω
Differential input voltage
min. 0.5 V
Counting frequency, max.
500 kHz
Counter input 24 V
Input voltage, for signal "0"
-30 to +5 V
Input voltage, for signal "1"
+11 to +30 V
Input current, for signal "1", typ.
9 mA
Counting frequency, max.
200 kHz
Minimum pulse width
>= 2.5 µs (200 kHz); <= 25 µs (20 kHz) (parameterizable)
Parameter
Remark
Assigned binary addresses: 64 bytes/64 bytes
Galvanic isolation
Galvanic isolation digital inputs
between the channels and the backplane bus
Yes; Optocoupler
Galvanic isolation digital outputs
between the channels and the backplane bus
Yes; Optocoupler
Galvanic isolation counter
between the channels and the backplane bus
Yes; Optocoupler
Permissible potential difference
between different circuits
75 VDC / 60 VAC
Isolation
Isolation checked with
500 V
Connection method
required front connector
1x 48-pin
Dimensions
Width
25 mm
Height
290 mm
Depth
210 mm
Weight
Weight, approx.
650 g
No comment |