PLC 4 PT100 Module Delta DVP04PT-S Delta NewDVP04PT-S Delta PLC 4 point RTD 0.1 degree resolution Temperature Measurement Module Original brand new
IntroductionDVP04PT-S is able to receive 4 points of platinum temperature sensors and convert them into 16-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program, the data in DVP04PT-S can be read and written. There are many 16-bit control registers (CR) in DVP04PT-S. The power unit is separate from it and is small in size and easy to install.
Electrical Specification
Power supply voltage
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Max. rated power
consumption
2W, supplied by external power
Operation/storage
Operation: 0°C~55°C (temp.), 5~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
Vibration/shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Series connection to
DVP-PLC MPU
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Functional Specifications
DVP04PT-S
Celsius (°C)
Fahrenheit (°F)
Analog input channel
4 channels per module
Sensors type
2-wire/3-wire PT100/ Ni100/ PT1000/ Ni100 3850 PPM/°C (DIN 43760 JIS C1604-1989)
Current excitation
1.53mA / 204.8uA
Temperature input range
Please refer to the temperature/digital value characteristic curve.
Digital conversion range
Please refer to the temperature/digital value characteristic curve
Resolution
16 bits (0.1°C)
16 bits (0.1°F)
Overall accuracy
+-0.6% of full scale during 0 ~ 55°C (32 ~ 131°F)
Response time
200ms × channels
Isolation method
Isolation between digital and analog circuitry. There is no isolation between channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
Isolation method
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Digital data format
2’s complement of 16-bit
Average function
Yes (CR#2 ~ CR#5)
Self diagnostic function
Yes
Communication mode
(RS-485)
Yes (CR#32). RS-485 is disabled when the DVP04PT-S is connected in series with an MPU.