No comment |
E5CC-QX2ASM-800 OMRON Thermostat NEWOMRON Thermostat E5CC-QX2ASM-800
Product Description:
Large White PV Display That's Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications.
Specifications:
Indication accuracy
Thermocouple: (± 0.3% of indicated value or ± 1°C, whichever is greater) ± 1 digit max. *1
(at the ambient temperature of
Platinum resistance thermometer: (± 0.2% of indicated value or ± 0.8°C, whichever is greater) ±
23°C)
1 digit
Analog input: ± 0.2% FS ± 1 digit max.
CT input: ± 5% FS ± 1 digit max.
Transfer output accuracy
± 0.3% FS max.
Remote SP Input Type
± 0.2% FS ± 1 digit max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II): (± 1% of PV or ± 10°C, whichever is greater) ± 1 digit max.
Other thermocouple input: (± 1% of PV or ± 4°C, whichever is greater) ± 1 digit max. *3
Platinum resistance thermometer: (± 1% of PV or ± 2°C, whichever is greater) ± 1 digit max.
Analog input: (± 1%FS) ± 1 digit max.
CT input: (± 5% FS) ± 1 digit max.
Influence of voltage *2
Remote SP input: (± 1% FS) ± 1 digit max.
Input sampling period
50 ms
Hysteresis
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Proportional band (P) for cooling
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Affect of signal source resistance
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Malfunction
10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Destruction
Shock resistance
100 m/s2, 3 times each in X, Y, and Z directions
Malfunction
300 m/s2, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.4 or higher
Setup Tool port
E5CC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer with the port on the top panel of the E5CC. *6
Standards
Approved standards
UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL)
Conformed standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *7
EMC
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1.The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°Cmax. is not specified. The indication accuracy of B thermocouples in the 400 to 800°Crange is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
*2.Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3.K thermocouple at -100°C max.: ±10°C max.
*4."EU" stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
*5.The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6.External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*7.Refer to information on maritime standards in Shipping Standards for E5[]N/E5[]N-H on Data Sheet for compliance with Lloyd's Standards.