DVP06XA-E2 Delta PLC 4AI 2AO 14-bit resolution Analog I/O Module Original brand new


Introduction

DVP06XA-E2 mixed analog input/output module receives external 4 points of analog input signals (voltage or current) and converts them into 16-bit digital signals. For the analog signal output, DVP06XA-E2 receives 2 groups of 16-bit digital data coming from the PLC MPU and converts the digital data into 2 points of analog output signals (voltage or current). In addition, you can access the data in the module by applying FROM/TO instructions or read the average value or write the output value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).

Electrical Specifications

DVP06XA-E2

Power supply voltage

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Max. rated power consumption

2.5W, supplied by external power source

Connector

European standard removable terminal block (Pin pitch: 5mm)

Operation/storage

Operation: 0°C~55°C (temp.), 5~95% (humidity), Pollution degree2

Storage: -25°C~70°C (temp.), 5~95% (humidity)

Vibration/shock immunity

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)

Series connection to DVP-PLC MPU

The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functions

Digital data format

2’s complement of 16 bits

Response time

400us / each channel

Overall accuracy

+-0.5% when in full scale within the range of (25°C, 77°F);  

+-1% when in full scale within the range of (0 ~ 55°C, 32 ~ 131°F)

Isolation

Optical coupler isolation between digital circuits and analog circuits.

No isolation among analog channels.

500VDC between digital circuits and Ground. 500VDC between analog circuits and Ground. 500VDC between analog circuits and digital circuits. 500VDC between 24VDC and Ground