Product Description:
Installation and assembling:
To ensure adequate cooling, the device must be installed vertically, with the input and output terminals at the bottom. Be sure to leave a minimum free space of 50 mm (2 in.) above and below the device. The supply voltage (120/230 V AC) must be connected in accordance with IEC 60364 and EN 50178. A protective device (fuse) and an insulating device for disconnecting the power supply must be provided. In Ex - applications must be guaranteed that installation is according to protection class IP 54.
Danger:
The mains switch has to be switched off and prevented from being switched on again before installation or maintenance. If these rules are not adhered to, contact with live parts or improper use can result in death or severe personal injury.
construction:
The SITOP 24 V/10 A power supply is a built-in unit. The relevant DIN/VDE regulations or equivalent local regulations must be observed during installation.
Primary switched-mode power supply for mounting directly by srews or on a DIN EN 50022-35x15/7.5 standard. For connection with firm wiring to 120 or 230 V, 50/60 Hz single-phase AC system.
Output voltage +24 V DC, potential-free, protected against short-circuit and open-circuit conditions.
Parallel connection of two similar devices to increase the power is permitted (provided the difference of the output voltages is < 0,2 % and the line impedances are equal to the load).
Technical specifications:
Specifications valid for input voltage 230 V AC and ambient temperature +25 °C, unless otherwise stated. They are subject to change without prior notice.
Features:
Type: 24 V/10 A
Order no.: 6EP1334-2AA01
Input:
Rated voltage Vin: 120/230 V AC
Voltage range: 85-132/170-264 V AC
Line frequency range: 47...63 Hz
Mains buffering: > 20 ms
Rated current Iin: 4.1/2.4 A
Protection in the mains supply line: 10 A Char. C
Output:
Rated voltage Vout: 24 V DC
Residual ripple/spikes: < 150/240 mVpp
Setting range: 22,8...28 V DC
Rated current Iout: 10A
- range up to 60 °C at ≤ 24 V DC 0...Iout
- range up to 50 °C at > 24 V DC 0...Iout
- range up to 45 °C at ≤ 24 V DC 0...1.2xIout
- range up to 35 °C at > 24 V DC 0...1.2xIout
Current limitation: typ. 13 A
Dynamic current limitation: 15 A/5 sec
Efficiency at full load: typ. 90 %
Enviromental conditions:
Transportation and storage -40 °C...+85 °C
temperature: ?
Ambient temperature during 0 °C...+60 °C
operation: ?
Shock and vibration 15g, 11ms (EN 60068-2-27) und 0,0053g2/Hz, 5-200 Hz, random (EN 60068-2-64)
Degree of protection: IP 20
Pollution degree environment: 2
Humidity rating: Climate category 3K3 acc. to EN 60721, relative air humidity 5...95 %, without condensation
EMC interference emission: EN 61000-6-4
EN 55022: Class B
EMC interference immunity: EN 61000-6-2, EN 61000-4-2/-3/-4/-5/-6/-11
Safety:
Protection class: I
Galvanic insulation SELV output voltage acc. to EN 60950 and EN 50178, Transformer corresponds EN 61558-2-
primary/secondary: 17, Protection against overvoltage at internal failure: Vout < 33 V from version 2”
Certificates:
CE CE marking acc. to 98/336 EEC and 73/23 EEC and 94/9/EEC
UL/CSA UL 508 (Listed, File E197259), CSA C22.2 No 14, No 60950-1-03
C-Tick AS/NZS 2064:1997
Directive 94/9/EG Konformitätsaussage nach EN 60079-15: ATEX94/9/EC Kat.3;Eex, nA, II, T4 U