No comment |
H5F-B AC100-240V OMRON Time Relay NEWOMRON Time Relay H5F-B AC100-240V
Product Description:
Specify the operation days.
(However, you can set only one pattern of operation days and specified days.)
Up to 12 ON/OFF operations (24 for pulse-output operation).
Special holidays can be handled easily with the holiday setting function.
Adjustments for sudden schedule changes can be made easily using output override and automatic return operation.
The operation program can be checked easily with the program check function.
Enables pulse output operation and summer time setting.
Incorporates finger-safe terminals.
Conforms to UL, CSA, and CE marking.
Meets a variety of mounting requirements: flush mounting, surface mounting, and DIN track mounting.
Specifications:
Accuracy of
±0.01% ±0.05 s max. (see note 1)
operating time
Setting error
Influence of voltage
Influence of
temperature
Time accuracy
±15 s per month (at 25°C)
Memory protection
Continuous use: 5 years min. (at 25°C); Power-interruption rate of 50%: 10 years min. (at 25°C) (see note 2) (lithium battery)
Insulation resistance
100 MΩ min. (between current-carrying terminals and exposed non-current-carrying metal parts, between operating power supply circuit and control output circuit and between non-continuous contacts)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts and between operating power supply circuit and control output circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Noise immunity
1.5 kV (between power terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Vibration resistance
Destruction: 10 to 55 Hz with 0.375-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Malfunction: 10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions
Shock resistance
Destruction: 300 m/s2 3 times each in 6 directions
Malfunction: 100 m/s2 3 times each in 6 directions
Ambient temperature
Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical (at 20°C):
100,000 operations min.
Electrical (at 20°C):
50,000 operations min. (15 A, 250 VAC, resistive load)
50,000 operations min. (1 HP, 250 VAC, motor load)
50,000 operations min. (10 A, 250 VAC, inductive load (cosΦ = 0.7))
50,000 operations min. (100 W, 100 VAC, lamp load)
10,000 operations min. (300 W, 100 VAC, lamp load)
Approved safety
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
standards
Conforms to VDE0106/P100 (finger protection).
Conforms to Electrical Appliance and Material Safety Law (for Japan)
EMC
(EMI): EN61326
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS): EN61326
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2), 8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz, 1.4 to 2 GHz) (level 3)
Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (according to EN61000-6-2)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3), 1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 2); 2 kV line to ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Immunity Magnetic Power Field: EN61000-4-8: 30 A/m
Case color
Light gray (Munsell 5Y7/1)
Weight
H5F-B: approx. 115 g; H5F-KB: approx. 160 g; H5F-FB: approx. 130 g
Note:
1.The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is ±0.01%±0.05 s max. ±0.01% also indicates an error in the time interval of a set time.
2.The total time when power is not being supplied.