H5CX-A11D-N AC?DC24V OMRON Timer NEWOMRON Timer H5CX-A11D-N AC?DC24V
Product Description:
DIN 48 × 48-mm Multifunction Digital Timer/2-stage Digital Timer
Specifications:
Accuracy of operating
Power-ON start: ±0.01% ±50 ms max. (See note 1.)
time and setting error
Signal start: ±0.005%±30 ms max. (See note 1.)
(including temperature
Signal start for transistor output model: ±0.005%±3 ms max. (See note 1 and 2.)
and voltage influences)
If the set value is within the sensor waiting time at startup the control output of the H5CX will not turn ON until the sensor waiting time passes.
Note:
1. The values are based on the set value.
2. The value is applied for a minimum pulse width of 1 ms.
Insulation resistance
100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and between non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuits for the models other than H5CX-[]D-N
1,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuits for H5CX-[]SD-N
2,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuits for other models
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC 1.5 kV for 24 VAC/12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/ 1 μs, 1-ns rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration
Destruction
10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each
resistance
Malfunction
10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each
Shock
Destruction
300 m/s2 in three directions, three cycles
resistance
Malfunction
100 m/s2 in three directions, three cycles
Life
Mechanical
10,000,000 operations min. (under no load at 1,800 operations/h and ambient temperature of 23°C)
expectancy
Electrical
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h and ambient temperature of 23°C) *
Weight
Approx. 115 g (Timer only)