Your Position: Home > Low Voltage > Relay > H3DE-M2 DC12 Timer NEW

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

H3DE-M2 DC12 Timer NEW

prevnext

H3DE-M2 DC12 Timer NEW
  • Market price: $ 227.7
  • Shop price: $ 69.0
  • Goods click count: 393
  • Total:
  • Quantity:
Add to cart collect
  

Description

H3DE-M2 DC12 OMRON Timer NEW

OMRON Timer H3DE-M2 DC12                      

Product Description:

Eight operating modes (H3DE-M) and four operating modes (H3DE-S) cover a wide range of applications.

Programmable contact enables the building of a self-holding relay circuit (-[]2 models).

A wide time setting range of 0.10 s to 120 h.

Specifications:

Accuracy of operating

±1% max. of FS (±1% ±10 ms max. at 1.2-s range) (see note 1)

time

Setting error

±10% ±50 ms max. of FS (see note 1)

Signal input time

50 ms min. (see note 1)

Influence of voltage

±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)

Influence of temperature

±2% max. of FS (±2%±10 ms max. at 1.2-s range)

Insulation resistance

100 MΩ min. at 500 VDC

Dielectric strength

Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.

Between control output terminals and operating circuit: 2,000 VAC for 1 min.

Between contacts of different polarities: 2,000 VAC for 1 min.

Between contacts not located next to each other: 1,000 VAC for 1 min.

Vibration resistance

Malfunction: 0.5-mm single amplitude at 10 to 55 Hz

Destruction: 0.75-mm single amplitude at 10 to 55 Hz

Shock resistance

Malfunction: 100 m/s2

Destruction: 1,000 m/s2

Contact material

AGNi+gold plating (Use the G6RN-1 at 12 VDC.)

Impulse withstand voltage

3 kV (between power terminals)

4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)

Noise immunity

Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) ±1.5 kV

Static immunity

Malfunction: 4 kV

Destruction: 8 kV

Life expectancy

Mechanical: 10 million operations min. (under no load at 1,800 operations/h)

Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)

(see note 2)

EMC

(EMI) EN61812-1

Emission Enclosure: EN55011 Group 1 class B

Emission AC Mains: EN55011 Group 1 class B

Harmonic Current: EN61000-3-2

Voltage Fluctuation and Flickering: EN61000-3-3

(EMS) EN61812-1

Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)

8 kV air discharge (level 3)

Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)

1 kV control port with capacitive clamp (level 3)

Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)

1 kV differential mode (level 3)

Degree of protection

IP30 (Terminal block: IP20)

Weight

120 g

Note:

1. With the H3DE-M[], if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes:

Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range

Setting error: ±10% +100/-50 ms max.

Signal input time: 100 ms min.

2. For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosΦ=1).

A maximum current of 0.1 A can be switched if L/R is 7 ms.

In both cases, a life of 100,000 operations can be expected.

The minimum applicable load is 10 mA at 5 VDC (failure level: P).

 

  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: