Your Position: Home > Low Voltage > Relay > H3CR-G8L AC100-120 Time Relay NEW

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

H3CR-G8L AC100-120 Time Relay NEW

prevnext

H3CR-G8L AC100-120 Time Relay NEW
  • Market price: $ 244.2
  • Shop price: $ 74.0
  • Goods click count: 384
  • Total:
  • Quantity:
Add to cart collect
  

Description

H3CR-G8L AC100-120 OMRON Time Relay NEW

OMRON Time Relay H3CR-G8L AC100-120            

Product Description:

A wide star-time range (up to 120 seconds) and star-delta transfer time range (up to 0.5 seconds).

Specifications:

Accuracy of operating time

±0.2% FS max.

Setting error

±5% FS ±50 ms max.

Accuracy of Star-delta transfer time

±25% FS + 5 ms max.

Reset voltage

10% max. of rated voltage

Influence of voltage

±0.2% FS max.

Influence of temperature

±1% FS max.

Insulation resistance

100 MΩ min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)

2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)

2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)

1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

Impulse withstand

3 kV (between power terminals)

voltage

4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)

Noise immunity

±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static immunity

Malfunction: 8 kV

Destruction: 15 kV

Vibration resistance

Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions

Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions

Shock resistance

Destruction: 980 m/s2 three times each in six directions

Malfunction: 294 m/s2 three times each in six directions

Ambient temperature

Operating: -10°C to 55°C (with no icing)

Storage: -25°C to 65°C (with no icing)

Ambient humidity

Operating: 35% to 85%

Life expectancy

Mechanical: 20 million operations min. (under no load at 1,800 operations/h)

Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)

EMC

(EMI) EN61812-1

Emission Enclosure: EN55011 Group 1 class A

Emission AC Mains: EN55011 Group 1 class A

(EMS) EN61812-1

Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)

8 kV air discharge (level 3)

Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)

Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3)

Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)

2 kV I/O signal-line (level 4)

Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)

2 kV line to ground (level 3)

Case color

Light Gray (Munsell 5Y7/1)

Degree of protection

IP40 (panel surface)

Weight

H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g

 

 

  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: