DVP06XA-H2 Delta PLC 4AI 2DO 12-bit resolution Analog Module Original brand newDVP06XA-H2 Delta PLC 4AI 2DO 12-bit resolution Analog Module Original brand new
Introduction
1. Thank you for choosing Delta DVP series PLC. DVP06XA-H2 is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-H2 receives 2 groups of 12-bit digital data from PLC MPU and converts them into 2 points of analog signal for output (in voltage/current).
2. You can select voltage or current input by wiring. Range of voltage input: ±10V DC (resolution: 5mV). Range of current input: +-20mA (resolution: 20uA).
3. You can also select voltage or current output by wiring. Range of voltage output: 0V ~ +10V DC (resolution: 2.5mV), Range of current output: 0mA ~ 20mA (resolution: 5uA).
Specifications
Analog/Digital (AD)
Voltage input
Current input
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
4 channels/module
Range of analog input
+-10V
+-20mA
Range of digital conversion
+-2,000
+-1,000
Resolution
12 bits (1LSB = 5mV)
11 bits (1LSB = 20uA)
Input impedance
200K? or higher
250?
Overall accuracy
+-0.5% when in full scale (25°C, 77°F)
+-1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Responding time
3ms × the number of channels
Isolation
Between analog and digital channels
Range of absolute input
+-15V
+-32mA
Digital data format
11 significant bits out of 16 bits are available; in 2’s complement
Average function
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20
Self-diagnosis
Upper and lower bound detection/channel
Digital/Analog (DA)
Voltage output
Current output
Analog output channel
2 channels/module
Range of analog output
0 ~ 10V
0 ~ 20mA
Range of digital data
0 ~ 4,000
0 ~ 4,000
Resolution
12 bits (1LSB = 2.5mV)
12 bits (1LSB = 5uA)
Overall accuracy
+-0.5% when in full scale (25°C, 77°F)
+-1% when in full scale within the range 0 ~ 55°C, 32 ~ 131°F
Output impedance
0.5? or lower
Response time
3ms × the number of channels
Max. output current
20mA (1K? ~ 2M?)
/
Tolerable load impedance
/
0 ~ 500?
Digital data format
11 significant bits out of 16 bits are available; in 2’s complement
Isolation
Internal circuit and analog output terminals are isolated by optical coupler.
No isolation among analog channels.
Protection
The voltage output is protected by short circuit. Please also be aware that being short circuit for too long period of time may cause damage on internal circuit. The current output can be open circuit.
Communication mode
(RS-485)
ASCII/RTU mode. Communication speed: 4,800 ~ 115,200 bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Power supply
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)., 3.5W supplied by external power
Environment
Operation/storage
Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
Vibration/shock immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)