No comment |
>
Control System >
VFD >
ABB VFD Drive >
ACS355-03E-38A0-4 ABB Inverter New in boxACS355-03E-38A0-4 ABB Inverter New in boxProduct Description:
ACS355 products from 0.37 to 22 kW / 0.5 to 30 hp supply voltage 200 - 480 V
ACS355 drives are designed for the machine building sector. In serial type manufacturing the consumed time per unit is critical. The drive is designed to be the fastest drive in terms of installation, setting parameters and commissioning. The basic product has been made as user-friendly as possible, yet providing high intelligence. The drive offers diverse functionality to cater for the most demanding needs.
Applications
Food & beverage
Material handling
Textile
Printing
Rubber & plastics
Woodworking
Features:
Ratings:
Type
Input
Output
Frame size
ACS355
x = E/U 1)I1N
I1N (480 V)
I2N
I2,1 min/10 min 2)
I2max
PN
A
A
A
A
A
kW
hp
1-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2
6.1
-
2.4
3.6
4.2
0.37
0.5
R0
01x-04A7-2
11.4
-
4.7
7.1
8.2
0.75
1
R1
01x-06A7-2
16.1
-
6.7
10.1
11.7
1.1
1.5
R1
01x-07A5-2
16.8
-
7.5
11.3
13.1
1.5
2
R2
01x-09A8-2
21
-
9.8
14.7
17.2
2.2
3
R2
3-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
03x-02A4-2
4.3
-
2.4
3.6
4.2
0.37
0.5
R0
03x-03A5-2
6.1
-
3.5
5.3
6.1
0.55
0.75
R0
03x-04A7-2
7.6
-
4.7
7.1
8.2
0.75
1
R1
03x-06A7-2
11.8
-
6.7
10.1
11.7
1.1
1.5
R1
03x-07A5-2
12
-
7.5
11.3
13.1
1.5
2
R1
03x-09A8-2
14.3
-
9.8
14.7
17.2
2.2
3
R2
03x-13A3-2
21.7
-
13.3
20
23.3
3
4
R2
03x-17A6-2
24.8
-
17.6
26.4
30.8
4
5
R2
03x-24A4- 2
41
-
24.4
36.6
42.7
5.5
7.5
R3
03x-31A0-2
50
-
31
46.5
54.3
7.5
10
R4
03x-46A2-2
69
-
46.2
69.3
80.9
11
15
R4
3-phase UN = 380…480 V (380, 400, 415, 440, 460, 480 V)
03x-01A2-4
2.2
1.8
1.2
1.8
2.1
0.37
0.5
R0
03x-01A9-4
3.6
3
1.9
2.9
3.3
0.55
0.75
R0
03x-02A4-4
4.1
3.4
2.4
3.6
4.2
0.75
1
R1
03x-03A3-4
6
5
3.3
5
5.8
1.1
1.5
R1
03x-04A1-4
6.9
5.8
4.1
6.2
7.2
1.5
2
R1
03x-05A6-4
9.6
8.1
5.6
8.4
9.8
2.2
3
R1
03x-07A3-4
11.6
9.7
7.3
11
12.8
3
4
R1
03x-08A8-4
13.6
11.4
8.8
13.2
15.4
4
5
R1
03x-12A5-4
18.8
15.8
12.5
18.8
21.9
5.5
7.5
R3
03x-15A6-4
22.1
18.6
15.6
23.4
27.3
7.5
10
R3
03x-23A1-4
30.9
26
23.1
34.7
40.4
11
15
R3
03x-31A0-4
52
43.7
31
46.5
54.3
15
20
R4
03x-38A0-4
61
51.2
38
57
66.5
18.5
25
R4
03x-44A0-4
67
56.3
44
66
77
22
30
R4
1) E = EMC filter connected (metal EMC filter screw installed),
U = EMC filter disconnected (plastic EMC filter screw installed), US parametrization.
2) Overloading not allowed through Common DC connection.
Type
Fuses
Size of copper conductor in cablings
ACS355-
x = E/UgG
UL Class
T (600 V)Supply
(U1, V1, W1)Motor
(U2, V2, W2)PE
Brake
(BRK+, BRK-)A
A
m?
AWG
m?
AWG
m?
AWG
m?
AWG
1-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
01x-04A7-2
16
20
2.5
14
0.75
18
2.5
14
2.5
14
01x-06A7-2
16/20 1)
25
2.5
10
1.5
14
2.5
10
2.5
12
01x-07A5-2
20/25 1)
30
2.5
10
1.5
14
2.5
10
2.5
12
01x-09A8-2
25/35 1)
35
6
10
2.5
12
6
10
6
12
3-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
03x-02A4-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-03A5-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-04A7-2
10
15
2.5
14
0.75
18
2.5
14
2.5
14
03x-06A7-2
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-07A5-2
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-09A8-2
16
20
2.5
12
2.5
12
2.5
12
2.5
12
03x-13A3-2
25
30
6
10
6
10
6
10
2.5
12
03x-17A6-2
25
35
6
10
6
10
6
10
2.5
12
03x-24A4- 2
63
60
10
8
10
8
10
8
6
10
03x-31A0-2
80
80
16
6
16
6
16
6
10
8
03x-46A2-2
100
100
25
2
25
2
16
4
10
8
03x-01A2-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-01A9-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-02A4-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-03A3-4
10
10
2.5
12
0.75
18
2.5
12
2.5
12
03x-04A1-4
16
15
2.5
12
0.75
18
2.5
12
2.5
12
03x-05A6-4
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-07A3-4
16
20
2.5
12
1.5
14
2.5
12
2.5
12
03x-08A8-4
20
25
2.5
12
2.5
12
2.5
12
2.5
12
03x-12A5-4
25
30
6
10
6
10
6
10
2.5
12
03x-15A6-4
35
35
6
8
6
8
6
8
2.5
12
03x-23A1-4
50
50
10
8
10
8
10
8
6
10
03x-31A0-4
80
80
16
6
16
6
16
6
10
8
03x-38A0-4
100
100
16
4
16
4
16
4
10
8
03x-44A0-4
100
100
25
4
25
4
16
4
10
8
Notes: If 50% overload capacity is needed, use the larger fuse alternative.
Dimensions, weights
Frame size
Dimensions and weights
IP20 (cabinet) / UL open
H1
H2
H3
W
D
Weight
mm
in
mm
in
mm
in
mm
in
mm
in
kg
lb
R0
169
6.65
202
7.95
239
9.41
70
2.76
161
6.34
1.2
2.6
R1
169
6.65
202
7.95
239
9.41
70
2.76
161
6.34
1.2
2.6
R2
169
6.65
202
7.95
239
9.41
105
4.13
165
6.5
1.7
3.7
R3
169
6.65
202
7.95
236
9.29
169
6.65
169
6.65
2.9
6.4
R4
181
7.13
202
7.95
244
9.61
260
10.24
169
6.65
5.1
11.2
Symbols
IP20 (cabinet) / UL open
H1 height without fastenings and clamping plate
H2 height with fastenings, without clamping plate
H3 height with fastenings and clamping plate
IP20 / NEMA 1
H4 height with fastenings and connection box
H5 height with fastenings, connection box and hood
Frame size
Dimensions and weights
IP20 / NEMA 1
H4
H5
W
D
Weight
mm
in
mm
in
mm
in
mm
in
mm
in
R0
257
10.12
280
11.02
70
2.76
169
6.65
1.6
3.5
R1
257
10.12
280
11.02
70
2.76
169
6.65
1.6
3.5
R2
257
10.12
282
11.10
105
4.13
169
6.65
2.1
4.6
R3
260
10.24
299
11.77
169
6.65
177
6.97
3.5
7.7
R4
270
10.63
320
12.60
260
10.24
177
6.97
5.7
12.6
Free space requirements:
Frame
sizeFree space required
Above
Below
On the sides
mm
in
mm
in
mm
in
R0…R4
75
3
75
3
0
0
Losses and cooling data:
Type
No comment |