No comment |
>
Control System >
PLC >
Other PLC >
GM4-CPUC LS PLC K300S Series CPU Module Maximum I/O points 3,584 NewGM4-CPUC LS PLC K300S Series CPU Module Maximum I/O points 3,584 NewPLCAGE: GM4-CPUC LS PLC K300S Series CPU Module Maximum I/O points 3,584 New
Introduction:
Powerful & compact module-type PLC K200S & K300S are module-type PLC that consist of various modules including basic module(CPU, Power, I/O), communication module and special module. And through various modules, user can configure the optimum system for industry environment
Features:
*Small- and medium-scale control with 1,024 points
*High-speed processing: 0.2us/step
*On-line editing
*Change I/O value by force
*Small- and medium-sized manufacture line control by network
*Downsizing and high performance
*Various special modules: analog, HSC, PID, positioning, etc
Specification:
Items
Specifications
Remarks
GM4-CPUA(B)
GM4-CPUC
Operation method
Cyclic operation of stored program, Interrupt task operation
I/O control method
Scan synchronous batch processing method (Refresh method)
Programming language
Ladder Diagram
Instruction List
Sequential Function Chart
Number of
instructions
Operator
21
Basic function
194
194 + Floating Point Arithmetic
Basic function block
11
Special function block
82
62
Processing
speed
Operator
0.2 µs / instruction
0.12 µs / instruction
Basic function
0.2 µs / Step
0.12 µs / Step
Basic function block
Programming memory capacity
128K byte
1M byte
Max. I/O points
2048 points
3,584 points
Max. I/O points memory mapping area
4,096(8,192) poi nts
32,768 points
Data memory
Direct variable area
4 to 32K byte
8 to 64K byte
Symbolic variable area
54(50)K byte - Direct variable area
428K byte -Direct variable area
Timer
No limitations in points.
Time range : 0.001 to 4,294,967.295 sec(1,193 hours)
1 point occupies 20 bytes
of symbolic variable area.
Counter
No limitations in points
Counting range : -32,768 to +32,767
1 point occupies 8 bytes
of symbolic variable area
Program
types
Numbers of program blocks
180
Initialization programs
2 (_INT, _H_INIT)
Task
Programs
Time driven tasks
8
32
External interrupt
tasks
8
Internal task
16
Error task
1 (_ERR_SYS)
Operation modes
RUN, STOP, PAUSE and DEBUG
Restart modes
Cold, Warm, Hot Restart
Self-diagnostic functions
Watch dog timer, Memory error detection, I/O error detection, Battery
error detection, Power supply error detection, etc.
Data protection method at power failure
Set to 'Retain' variables at data declaration.
Maximum extension stages
3
6
Internal current consumption
130mA
700mA
Weight
0.25 Kg
0.23 Kg
Application
Customer willing to use IEC language
LCD/PDP field
Auto (auto/car accessories) field
Raw materials(chemical/glass/iron/steel) field
Field of water treatment and boiler
Other hot items of this LS PLC K300S series for above applications:
Items
Module No.
Description
Remark
Main base boards
GM4-B04M
4 module
GM4-B06M
6 module
GM4-B08M
8 module
GM4-B12M
12 modules
No expansion
Expansion base boards
GM4-B04E
4 module
GM4-B06E
6 module
GM4-B08E
8 module
Power supply modules
GM4-PA1A
110VAC
5VDC:5A,24VDC:0.7A
GM4-PA2A
220VAC
GM4-PA1B
110VAC
5VDC:3A,24VDC:0.5A
GM4-PA2B
220VAC
GM4-PD3A
24VDC
5VDC:4A,24VDC:bypass
No comment |