Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: G7F-AT2A
- Weight: 0.20kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
LS (LG) Expansion Module G7F-AT2A
Product Description:
The G7F-AT2A is used with the CPU of GLOFA PLC GM7series and MASTERK80S series. Hereafter, they are called Analog Timer Module(A/T module). The A/T module performs on-delay operation for a setting time.
Features:
General Specifications | ||||||
No | Item | Specifications | Standard | |||
1 | Operating temperature | 0 ~ 55? | - | |||
2 | Storage temperature | -25 ~ 75? | ||||
3 | Operating Humidity | 5 ~ 95%RH, non-condensing | ||||
4 | Storage humidity | 5 ~ 95%RH, non-condensing | ||||
5 | Vibration | Occasional vibration | IEC 61131-2 | |||
Frequency | Acceleration | Amplitude | Sweep count | |||
10≤f∠57 Hz | - | 0.075 mm | 10 times in each direction for X, Y, Z | |||
57 ≤f≤150 Hz | 9.8? {1G} | - | ||||
Continuous vibration | ||||||
Frequency | Acceleration | Amplitude | ||||
10≤f∠57 Hz | - | 0.035 mm | ||||
57≤f≤150 Hz | 4.9?{0.5G} | - | ||||
6 | Shocks | *Maximum shock acceleration: 147? {15G} | IEC 61131-2 | |||
*Duration time :11 ms | ||||||
*Pulse wave:half sine wave pulse( 3 times in each of X, Y and Z directions ) | ||||||
7 | Noise immunity | Square wave impulse noise | ±1,500 V | LGIS Standard | ||
Electrostatic discharge | Voltage :4kV(contact discharge) | IEC 61131-2 IEC 1000-4-2 | ||||
Radiated electromagnetic field | 27 ~ 500 MHz, 10 V/m | IEC 61131-2 IEC 1000-4-3 | ||||
Fast transient & burst noise | All power modules | Digital I/Os ( Ue ≥ 24 V) | Digital I/Os (Ue < 24 V) Analog I/Os communication I/Os | IEC 61131-2 IEC 1000-4-4 | ||
2 kV | 1 kV | 0.25 kV | ||||
8 | Atmosphere | Free from corrosive gases and excessive dust | - | |||
9 | Altitude for use | Up to 2,000m | ||||
10 | Pollution degree | 2 or lower | ||||
11 | Cooling method | Self-cooling | ||||
Performance Specifications | |
Item | Specification |
Number of channels | 4 |
Output value range | 8 Bit (Digital output range: 0 ∼ 200) |
Setting type | Setting by variable resistance |
Accuracy of timer | ±2.0% (Accuracy about max. value) |
Operation method | Reading by means of using executive function block (AT2RD) |
Internal current consumption | 50? |
Number of module installment | Max 3 modules |
Weight | 200g |